6 Commissioning/start-up
6.8 Setting the output signal (S.Type)
How to proceed:
6.8.1 Output performance
The output signal behavior in the event of an abrupt change of the input signal is specified in
the following table and the figure.
Step Activity
1 Unlock the device.
Chapter 6.2 "Unlocking the device (enter the code).", page 42
2 "Turn" until "S.Type" appears in the bottom line.
3"Press"
Setting:
4.20A = Output signal 4 to 20 mA
0.20A = Output signal 0 to 20 mA
0.10U = Output signal 0 to 10 V
Output Dead time t1 Time constant t2
Current output < 200 ms at 50 Hz mains frequency
< 320 ms at 60 Hz mains frequency
70 ms
Voltage output < 200 ms at 50 Hz mains frequency
< 320 ms at 60 Hz mains frequency
80 ms