6 Commissioning/start-up
6.10 Setting the error signal of the analog output (S.Err)
In the event of errors (e.g. probe break or probe short-circuit), the analog output transmits the
signal configured here.
How to proceed:
Setting:
TIP!
An error signal for overrange or underrange is only transmitted on devices with analog output.
Step Activity
1 Unlock the device.
Chapter 6.2 "Unlocking the device (enter the code).", page 42
2 "Turn" until "S.Err" appears in the bottom line.
3"Press"
Type of signal Setting
4 to20 mA
= 3.4 mA
= 22 mA
0to20mA
= 0 mA
= 22 mA
0to10V
= 0 V
= 10.7 V