6 Commissioning/start-up
54
6.11 Behavior when the scaling range is exceeded
The standard signal range of the analog output is limited as per recommendation of Namur NE
43.
Example:
4to20mA (factory setting)
Type of signal lower limit upper limit
4to20mA 3.8mA 20.5mA
0to20mA 0mA 20.5mA
0to10V 0V 10.2V