Datasheet

2013-03-12/00535026
Data Sheet 403025 Page 2/11
JUMO GmbH & Co. KG
Delivery address: Mackenrodtstraße 14
36039 Fulda, Germany
Postal address:
36035 Fulda, Germany
Phone: +49 661 6003-0
Fax: +49 661 6003-607
E-mail: mail@jumo.net
Internet: www.jumo.net
JUMO Instrument Co. Ltd.
JUMO House
Temple Bank, Riverway
Harlow, Essex CM20 2DY, UK
Phone: +44 1279 635533
Fax: +44 1279 635262
E-mail: sales@jumo.co.uk
Internet: www.jumo.co.uk
JUMO Process Control, Inc.
6733 Myers Road
East Syracuse, NY 13057, USA
Phone: 315-437-5866
1-800-554-5866
Fax: 315-437-5860
E-mail: info.us@jumo.net
Internet: www.jumousa.com
Technical data
General
Input
Output
Reference conditions DIN 16086, DIN EN 60770 and DIN IEC 770/5.3
Sensor system Silicon sensor with stainless steel separating diaphragm
Pressure transfer medium
for measuring system filling medium 0 Without transfer medium
for measuring system filling medium 1 Silicon oil, FDA-compliant
Permissible load change > 10 million
Location
Mounting position Any
Calibration position Device standing vertically, process connection on bottom
Location-dependent zero point offset Zero point calibration possible locally or via setup.
for medium temperature 1 (up to 120 °C) 1mbar
for medium temperature 2 (up to 200 °C) 10 mbar
Display LCD, two-line with bar graph
Alignment Display unit can be rotated 90° at a time
Housing can be rotated ±160°
Size Display field 22 × 35 mm/font size 7 mm/5 digits
Color Black
Measurement unit display options
Input pressure mH
2
O, inH
2
O, inHg, ftH
2
O, mmH
2
O, mmHg, psi, bar, mbar, kg/cm
2
, kPa, Torr, MPa
Measurement value % or scaled with a freely adjustable measurement unit
Output current mA
Sensor temperature °C; °F
Additional display data Minimum pressure, maximum pressure, error, overrange, underrange, operating hours, device
parameters
Operation
Local With rotary knob and LCD
Setup program Via interface
Interface
Standard JUMO interface
a
a
The JUMO interface must not be used for instruments with ATEX Ex ia explosion protection! These instruments can be operated by the rotary
knob or via the HART
®
interface.
for output 410 (4 20 mA with HART®) JUMO interface
a
and HART
®
interface
Relative pressure
Nominal measuring range -600 to 600 mbar
rel.
-1 to 4 bar rel. -1 to 25 bar rel. -1 to 100 bar rel. -1 to 600 bar rel.
Overload capacity 6 bar 30 bar 150 bar 300 bar 1200 bar
Burst pressure 12 bar 60 bar 250 bar 400 bar 2000 bar
Absolute pressure
Nominal measuring range 0 to 0.6 bar abs. 0 to 4 bar abs. 0 to 25 bar abs. 0 to 100 bar abs.
Overload capacity 6 bar 30 bar 150 bar 300 bar
Burst pressure 12 bar 60 bar 250 bar 400 bar
Analog output
for output 405 4 to 20 mA, two wire
for output 410 4 to 20 mA, two wire with HART
®
Step response time T60 190 ms without damping
Damping adjustable, 0 to 100 s