Datasheet
V1.00/EN/00578870
Data Sheet 703571 Page 10/23
JUMO GmbH & Co. KG
Delivery address: Mackenrodtstraße 14
36039 Fulda, Germany
Postal address:
36035 Fulda, Germany
Phone: +49 661 6003-0
Fax: +49 661 6003-607
Email: mail@jumo.net
Internet: www.jumo.net
JUMO Instrument Co. Ltd.
JUMO House
Temple Bank, Riverway
Harlow, Essex CM20 2DY, UK
Phone: +44 1279 635533
Fax: +44 1279 635262
Email: sales@jumo.co.uk
Internet: www.jumo.co.uk
JUMO Process Control, Inc.
6733 Myers Road
East Syracuse, NY 13057, USA
Phone: 315-437-5866
1-800-554-5866
Fax: 315-437-5860
Email: info.us@jumo.net
Internet: www.jumousa.com
70357100T10Z002K000
Electrical data
Environmental influences
Case
Approvals/approval marks
Voltage supply
Connection
Voltage
At the back via screw terminals
AC/DC 24 V +30/-25%, 48 to 63 Hz or AC 110 to 240 V +10/-15 %, 48 to 63 Hz
Power consumption At voltage supply 230 V: max. 15 VA / 7 W
At voltage supply 24 V: max. 12 VA / 9 W
Inputs and outputs
Connection
Conductor cross section
At the back via screw terminals
Max. 2.5 mm
2
, wire or strand with end sleeve
Electrical safety According to DIN EN 61010-1
Overvoltage category III, pollution degree 2
Electromagnetic compatibility
Interference emission
Interference immunity
According to DIN EN 61326-1
Class A - For industrial applications only
Industrial requirements
Memory data recorder Memory cycle Recording interval
When recording:
4 analog signals
3 digital signals
1 s approx. 44 days
5 s approx. 220 days
10 s approx. 441 days
60 s approx. 2646 days (7 years, 91 days)
Ambient/storage temperature range -5 to +55 °C/-30 to +70 °C
Resistance to climatic conditions Humidity 3K3 (DIN EN 60721-3-3) with extended temperature range,
rel. humidity 95 % mid-year without condensation
Site Altitude maximum 2000m above sea level
Case type Plastic front frame with metal case barrel (for indoor use only)
Front frame dimensions 96 mm × 96 mm
Panel cut-out 92
+0.8
mm × 92+
0.8
mm according to DIN IEC 61554
Close mounting Spacing between the panel cut-outs, min. 35 mm horizontally and min. 80 mm verti-
cally
Panel thickness Max. 5 mm
Depth behind panel Max. 130 mm
Mounting Four mounting brackets
Operating position
(including the viewing angle of the TFT color screen)
Any
Horizontal ±65°, vertical +40 to -65°
Protection type Front IP66, rear IP20, according to DIN EN 60529
Weight (fully fitted) approx. 1000 g
Approval mark
Testing agency
Certificate/certification
number
Inspection basis Valid for
GL - hardware
GL - software
Germanischer Lloyd 11 172-14 HH Environmental Category C
EMC 1
All modules except
PROFINET-RT
c UL us Underwriters Laboratories 20150622-E201387 UL 61010-1 All modules
D
IN DIN CERTCO TR1238 DIN EN 14597 All modules except
PROFINET-RT