Manual

Table Of Contents
12
4 Technical data
4 Technical data
4.1 Electrical data
4.2 Inputs
4.3 Outputs
Voltage supply DC 24 V SELV
PNP, NPN, push-pull DC 9.6 to 36 V
IO-Link DC18to32V
Explosion protection Ex i DC 9.6 to 30 V
Current consumption
a
Idle mode 0.45 W
Switch operation with 2 outputs 15 W
IO-Link operation 0.5 W
Protection class 3
Overvoltage category II
Pollution degree 2
Electrical connection
Connection elements M12 plug connector
Connecting cable
Temperature resistance 90 °C
Electrical safety DIN EN 61010-1:2023
Requirements The device must be equipped with an electrical circuit that meets the require-
ments with regard to "Limited-energy circuits".
a
The device labeling indicates a maximum power consumption in switching mode with 2 outputs including self-con-
sumption. The actual power consumption depends on the connected load.
Hysteresis ±1 mm
Repeatability ±1 mm
Switch-on delay < 2 s, during this time the switching outputs are blocked
Switching delay Adjustable 0.3 to 60 s
When the sensor is covered 0.5 s
When the sensor is uncovered 1 s
Filter time constant Adjustable 0 to 100 s
Number
For IO-Link operation 1 (output signal according to IO-Link communication standard version 1.1)
For switching operation 2 (SIO mode; SIO = standard IO)
With PNP, NPN, push-pull 2
Configuration options Hysteresis or window function, switching function, NC contact or NO contact,
output p-switching (PNP) or n-switching (NPN), switch-on and switch-off delay,
pulse-width modulation (PWM), pollution degree detection, wet test with medi-
um
Pulse-width modulation (PWM)
Period duration adjustable 50 to 1000 ms
Mark-to-space ratio
0 t
o 100 %
Switching cu
rrent 200 mA per output
Voltage drop at switching transistor 1 V