Devices in stock: JUMO heatTHERM-AT
Room thermostat temperature monitor / temperature monitor TW/TW, type 6
Flue gas temperature monitor with mounting sleeve, design 5
Type 603070/0202
a
a
Further design versions (control range, switching differential, process connection) upon request - minimum order quantity 100 pieces. Thermowells page 15.
•Protection type IP 54
Wall mounting
Switching value control through in-
spection window in the case lid
Part no. Type Control range °C Capillary
mm
Probe−∅
(d) × L mm
Switching
differential
Process connection
60003212 JUMO
heatTHERM-AT/
0202
-10 to +40
- - - - 1.5 - 2 K Spiral probe
60003213
0 to +50
Type 603070/0020
a
a
Further design versions (control range, switching differential, process connection) upon request - minimum order quantity 100 pieces. Thermowells page 15.
Switching value check through in-
spection window in the case lid
Max. allowable probe temperature
+600 °C
Approval as ATW with capillary
break protection according to
DIN EN 14597
Time constant t0.632 45 sec. in
flue gas
Part no. Type Control range °C Capillary
mm
Probe−∅
(d) × L mm
Switching
differential
Process connection
60003390
JUMO
heatTHERM-AT/
0020
+20 to +280 - - 6 mm Approx. 18 K Intermediate piece with mounting flange