Datasheet

10.02/00411125
Data Sheet 70.1050M. K. JUCHHEIM GmbH & Co • 36035 Fulda, Germany Page 2/3
Technical data
Measurement input
Ambient conditions
Relay output
Supply
Housing
Electrical data
Designation Range Accuracy Over/underrange
Pt100 EN 60 751 -200 to +500°C 0.1% is recognized
Pt1000 DIN -200 to +500°C 0.1%
KTY2X-6 -50 to 150 °C 1%
Connection circuit 2-wire circuit via screw terminals, for wire cross-sections up to 2.5 mm
2
Sampling time 250 msec
Input filter 1st order digital filter; filter constant adjustable from 0 to 99.9sec
Lead compensation adjustable via the parameter Lead compensation resistor
Temperature offset adjustable via the parameter Temperature offset
Special features display can be switched to °F (Fahrenheit)
Ambient temperature range 0 to +55°C
Storage temperature range -40 to +70°C
Temperature error 100ppm per °C of range
Climatic conditions 75% rel. humidity annual mean, no condensation
Changeover contact 150,000 operations at 10A 250V 50Hz resistive load
800,000 operations at 3A 250V 50Hz resistive load
Connection via screw terminals, for wire cross-sections up to 2.5 mm
2
Supply voltage 230V AC +10/-15%, 48 — 63Hz
115V AC +10/-15%, 48 — 63Hz
12V DC +15/-15%
24V DC +15/-15%
Power consumption <1VA
Material polycarbonate
Mounting on 35mm x 7.5mm DIN rail to EN 50 022
Operating position unrestricted
Weight approx. 110gm
Protection IP20
Flammability class UL 94 V0
Data backup EEPROM
Electromagnetic compatibility
interference emission
immunity to interference
EN 61 326
Class B
to industrial requirements
Electrical safety to EN 61 010, Part 1, overvoltage category III, pollution degree 2