Datasheet

V3.00/EN/00542385
Data Sheet 701155 Page 19/19
70115500T10Z000K000
-802*PE+&R.*
'HOLYHU\DGGUHVV 0DFNHQURGWVWUDH
)XOGD*HUPDQ\
3RVWDODGGUHVV
)XOGD*HUPDQ\
3KRQH 
)D[ 
(PDLO PDLO#MXPRQHW
,QWHUQHW ZZZMXPRQHW
-802,QVWUXPHQW&R/WG
-802+RXVH
7HPSOH%DQN5LYHUZD\
+DUORZ(VVH[&0'<8.
3KRQH 
)D[ 
(PDLO VDOHV#MXPRFRXN
,QWHUQHW ZZZMXPRFRXN
-8023URFHVV&RQWURO,QF
0\HUV5RDG
(DVW6\UDFXVH1<86$
3KRQH 
)D[ 
(PDLO LQIRXV#MXPRQHW
,QWHUQHW ZZZMXPRXVDFRP
Order details
1. The first digit on the measurement input means single probe "1" or double probe "2"
Basic type
701155
Safety temperature limiter/monitor (STB)/(STW) according to DIN EN 14597
with SIL, PL, and IPL approval
Version
8
Default setting
9
Configured according to customer specifications
National language
01
German (default setting)
02
English
03
French
Switching behavior
0251
Safety temperature monitor max. alarm (opening function)
0252
Safety temperature monitor min. alarm (closing function)
0253
Safety temperature limiter max. alarm (opening function)
0254
Safety temperature limiter min. alarm (closing function)
Measurement input
1
(programmable)
1003 1x Pt100 in two-wire circuit
2001 2x Pt100 in three-wire circuit (default setting)
2003 2x Pt100 in two-wire circuit
2005 2x Pt1000 in two-wire circuit
2006 2x Pt1000 in three-wire circuit
2036 2x W5Re-W26Re "C"
2037 2x W3Re-W25Re "D"
2039 2x Cu-CuNi “T”
2040 2x Fe-CuNi "J"
2041 2x Cu-CuNi “U”
2042 2x Fe-CuNi "L"
2043 2x NiCr-Ni "K"
2044 2x Pt10Rh-Pt "S"
2045 2x Pt13Rh-Pt "R"
2046 2x Pt30Rh-Pt6Rh “B”
2048 2x NiCrSi-NiSi "N"
1053 1x 4 to 20 mA
2053
2x 4 to 20 mA
Voltage supply
23
AC 110 to 240 V +10 % /-15 %, 48 to 63 Hz
25
AC/DC20to30V, 48to63Hz
Ignition protection type
044
045
[Ex ia] associated apparatus, installation outside the Ex-area
[Ex eb, tb] associated apparatus, "eb" for gas, "tb" for dust,
installation outside the Ex-area
Analog output (configurable)
001
0to 20mA
005
4 to 20 mA (default setting)
040
0to 10V
070
2to 10V
Extra code
059
SIL, PL, IPL approval is always present
062
DNVGL approval
701155/ 8- 01 - 0253 - 2001 - 23- 044 - 005/ 059
Accessories
Item Sales no.
Setup program, multilingual 70/00548742
USB cable 70/00506252
External unlocking button RT 70/97097865