Data Sheet 702030 Page 3/12
Controller parameters
All the parameters and their meanings are included in the table. Some parameters may be missing or meaningless for a particular type of controller.
Technical data
Thermocouple input
RTD temperature probe input
Parameters Value range Factory setting Meaning
Proportional band 1 (Pb1) 0 to 9999 digit 0 digit Size of the proportional band
The controller structure is not effective with Pb = 0 (behavior identical
to limit value monitoring). For a continuous controller, Pb1 must be > 0.
Proportional band 2 (Pb2) 0 to 9999 digit 0 digit
Derivative time (dt) 0 to 9999 s 80 s Influences the differential component of the controller output signal
Reset time (rt) 0 to 9999 s 350 s Influences the integral component of the controller output signal
Cycle time 1 (Cy1) 0 to 999.9 s 20.0 s When using a switched output, the cycle time should be chosen so that
the energy supply to the process is as continuous as possible without
overloading the switching elements.
Cycle time 2 (Cy2) 0.0 to 999.9 s 20.0 sec
Contact spacing (db) 0.0 to 999.9 digit 0.0 digit Spacing between the two control contacts of the three-state controller
Switching differential 1 (HyS1) 0.0 to 999.9 digit 1.0 digit Switching differential of a switching controller with proportional band
Pb = 0 (behavior identical to limit value monitoring)
Switching differential 2 (HyS2) 0.0 to 999.9 digit 1.0 digit
Working point (y0) -100 to +100 % 0 % Output level for P and PD controller (if x = w then y = y0)
Output value limit 1 (y1) 0 to 100 % 100 % Maximum output value limit (only effective if Pb > 0)
Output value limit 2 (y2) -100 to +100 % -100 % Minimum output value limit (only effective if Pb > 0)
Description Standard Measuring range
a
a
This information refers to the ambient temperature of 20 °C.
Measuring accuracy
b
b
Incl. measuring accuracy at the cold junction.
The accuracy values refer to the measuring range.
Ambient temperature
influence
Fe-CuNi "L"
Fe-CuNi "J"
Cu-CuNi "T"
NiCr-Ni "K"
NiCr-CuNi "E"
NiCrSi-NiSi "N"
Pt10Rh-Pt "S"
Pt13Rh-Pt "R"
EN 60584
EN 60584
EN 60584
EN 60584
EN 60584
EN 60584
EN 60584
-150 to +900 °C
-200 to +1200 °C
-200 to +400 °C
-200 to +1372 °C
-200 to +1000 °C
-100 to +1300 °C
-40 to +1768 °C
-40 to +1768 °C
0.4 %
0.4 %
0.4 %
0.4 %
0.4 %
0.4 %
0.4 %
0.4 %
100 ppm/K
100 ppm/K
100 ppm/K
100 ppm/K
100 ppm/K
100 ppm/K
100 ppm/K
100 ppm/K
Cold junction: KTY internal
Designation,
connection type
Measuring range Measuring accuracy
a
Ambient temperature
influence
Pt100 EN 60751
2-wire connection
3-wire connection
-200 to +650 °C
0.4 %
0.4 %
50 ppm/K
Pt1000 EN 60751
2-wire connection
3-wire connection
-200 to +650 °C
0.4 %
0.4 %
50 ppm/K
KTY, R
25
= 1000 Ω
2-wire connection
-50 to +150 °C
1.0 %
50 ppm/K
KTY, R
25
= 2000 Ω
2-wire connection
-50 to +80 °C
1.0 %
50 ppm/K
Cu-50
3-wire connection
-50 to +200 °C
1.0 %
50 ppm/K