Controller
Timer
Electrical data
Requirements for core-end ferrules and cable lugs
Case and ambient conditions
Controller type Two-state controller, three-state controller, continuous controller
Controller structures P/PI/PD/PID
Sampling rate 250 ms
A/D converter 16-bit resolution
Accuracy 0.8 % ± 10 ppm/K ± 250 ms
Voltage supply (switch mode PSU) AC 110 to 240V +10/-15 %, 48 to 63Hz
AC/DC 20 to 30V, 48 to 63Hz
Electrical security Acc. to DIN EN 61010, part 1; overvoltage category III, pollution degree 2
Power consumption Max. 14 VA
Electrical connection On the rear via screw terminals; with core-end ferrule of a pipe shape, open cable lug or pin cable lug
Conductor cross section Fine-strand 0.25 to 1.5 mm
2
Tightening torque 0.5 Nm
Electromagnetic compatibility Acc. to DIN EN 61326-1
Interference emission Class A - only for industrial use -
Interference immunity Industrial requirements
Setup interface USB socket, type Mini-B 5-pole
Core-end ferrule Pipe shape, without plastic sheath acc. to DIN 46228 part 1,
with plastic sheath acc. to DIN 46228 part 4
Cable lug Open crimp cable lug, dimensionally adapted to DIN 46237 for closed crimp cable lugs
Pin cable lug Acc. to DIN 46231
For UL applications Use of the cable lugs or ferrules acc. to UL 486A-B (UL listed or recognized)
Case type Plastic case for panel mounting acc to. IEC 61554 (indoor use)
Dimensions (front) LC100: 48 mm x 48 mm; LC200: 48 mm x 96 mm (portrait format);
LC300: 96 mm x 96 mm
Weight (fully fitted) LC100: approx. 150 g; LC200: approx. 200 g; LC300: approx. 300 g
Protection class Acc. to DIN EN 60529, at the front IP 65, at the rear IP 20
Operating position Any
Panel cut-out LC100: 45 mm x 45 mm; LC200: 45 mm x 92 mm;
LC300: 92 mm x 92 mm
Minimum spacing horizontal/vertical LC100: 11 mm / 30 mm (65 mm with USB cable);
LC200/LC300: 22 mm / 30 mm (65 mm with USB cable)
Depth behind panel LC100: max. 95 mm; LC200/LC300: max. 80 mm
Ambient/storage temperature range -5 to +55 °C / -40 to +70 °C
Climatic conditions Rel. humidity < 90 % annual average, without condensation
Site altitude Up to 2000 m above sea level