Datasheet

V2.00/EN/00710338/2019-11-07
Page 1/24Data Sheet 706521
70652100T10Z001K000
-802*PE+&R.*
'HOLYHU\DGGUHVV 0DFNHQURGWVWUDH
)XOGD*HUPDQ\
3RVWDODGGUHVV
)XOGD*HUPDQ\
3KRQH 
)D[ 
(PDLO PDLO#MXPRQHW
,QWHUQHW ZZZMXPRQHW
-802,QVWUXPHQW&R/WG
-802+RXVH
7HPSOH%DQN5LYHUZD\
+DUORZ(VVH[&0'<8.
3KRQH 
)D[ 
(PDLO VDOHV#MXPRFRXN
,QWHUQHW ZZZMXPRFRXN
-8023URFHVV&RQWURO,QF
0\HUV5RDG
(DVW6\UDFXVH1<86$
3KRQH 
)D[ 
(PDLO LQIRXV#MXPRQHW
,QWHUQHW ZZZMXPRXVDFRP
JUMO LOGOSCREEN 601
Paperless Recorder with Touchscreen
Brief description
The JUMO LOGOSCREEN 601 paperless recorder is characterized by an intuitive, icon-based
operation and visualization concept that makes it easy to operate.
Different versions of the JUMO LOGOSCREEN 601 are available for process data recording.
The scalability allows for flexible adaptation to various customer requirements: from the device
version without measurement input (24 process values via interface) through to different device
versions with up to 6 measurement inputs (universal analog inputs), 2 analog outputs, 12 digital
inputs, 12 individually switchable digital inputs/outputs. A relay output is available as standard.
The version with FDA-compliant data recording fulfills all requirements according to 21 CFR Part
11.
In order to display the recorded data, the JUMO LOGOSCREEN 601 features various visualiza-
tions. In addition, the user can use the setup program to create up to 6 separate process screens
with up to 100 objects per process screen according to his individual requirements. For batch-
based processes, a special batch recording is available which enables the storage of additional,
batch-related information. The extra code "structured text" allows for the creation of individual
measurement and recording applications.
Type 706521/...
Block diagram
Setup programm
PCC, PCA3000
PCS, PCAT
Software
Internal channels
6 math channels (optional)
6 logic channels (optional)
6 counters/integrators
2 high-speed counters
ST code (optional)
Inputs/outputs
Optionen 1 und 2:
3 analog inputs,
6 digital inputs,
1 analog output
each
12 digital inputs/outputs,
incl. 2 high-speed counting inputs
(up to 12.5 kHz)
Option 3:
Display/operation
JUMO LOGOSCREEN 601
Voltage supply
Display
Operation
14.5 cm (5.7”) TFT color screen
640 x 480 pixel,
65536 colors
Touchscreen (resistive)
As standard:
24 external analog inputs and
24 external digital inputs and
14 external texts (10 batch texts,
4 event texts)
Inputs via interface
As standard:
1 relay (changeover contact)
Relay output
AC 110 to 240 V +10/-15 %,
48 to 63 Hz
AC/DC 20 to 30 V, 48 to 63 Hz
Interfaces
As standard:
1x Ethernet 10/100 MBit/s
1x USB host (flash drive)
1x USB device (setup)
1x RS232/RS485
(Modbus master/slave or
barcode scanner)
Optional:
1x PROFINET IO Device
Internal memory
(data transfer via interface
or USB flash drive)
: 1 GByte
Measurem.-data memory
Special features
Intuitive touch operation
Up to 2 analog outputs
Up to 6 customer-specific process
screens
PROFINET IO device interface (extra
code)
Integrated web server for online visual-
ization as on device
Recording of a batch report
Limit value monitoring function (24 chan-
nels)
Flow measurement (2 channels, option)
2 counter inputs (max. 12.5 kHz, option)
User-specific application using structured
text (ST code; extra code)
Automatic data readout via PCA Commu-
nication Software PCC
Data recording compliant with FDA 21
CFR Part 11 (extra code)
Manipulation detection with digital certifi-
cate (extra code)
PC programs for data evaluation and ac-
cess control
AMS2750/CQI-9 (extra code)
Wide operating temperature range
Approvals and approval marks (see "Technical data")

Summary of content (24 pages)