70652100T10Z001K000
Technical data
Analog inputs
General
Thermocouples
Number Max. 6 (see connection diagram)
A/D converter 24 bit delta-sigma
Sampling rate Up to 6 channels: 125 ms
Input filter Digital filter, 2nd order; filter constant can be set from 0 to 100.0 s
Galvanic isolation See "Galvanic isolation"
Designation Type Standard ITS Measuring range Accuracy
a
a
Accuracy refers to the measuring range
Fe-CuNi "L" DIN 43710 (1985) IPTS-68 -200 to +900 °C 0.1 %
Fe-CuNi "J" DIN EN 60584-1:2014
IEC 60584-1:2013
ITS-90 -210 to +1200 °C 0.1 % from -100 °C
Cu-CuNi "U" DIN 43710 (1985) IPTS-68 -200 to +600 °C 0.1 % from -100 °C
Cu-CuNi "T" DIN EN 60584-1:2014
IEC 60584-1:2013
ITS-90 -270 to +400 °C 0.1 % from -150 °C
NiCr-Ni "K" DIN EN 60584-1:2014
IEC 60584-1:2013
ITS-90 -270 to +1300 °C 0.1 % from -80 °C
NiCr-CuNi "E" DIN EN 60584-1:2014
IEC 60584-1:2013
ITS-90 -270 to +1000 °C 0.1 % from -80 °C
NiCrSi-NiSi "N" DIN EN 60584-1:2014
IEC 60584-1:2013
ITS-90 -270 to +1300 °C 0.1 % from -80 °C
Pt10Rh-Pt "S" DIN EN 60584-1:2014
IEC 60584-1:2013
ITS-90 -50 to +1768 °C 0.15 % from 100 °C
Pt13Rh-Pt "R" DIN EN 60584-1:2014
IEC 60584-1:2013
ITS-90 -50 to +1768 °C 0.15 % from 100 °C
Pt30Rh-Pt6Rh "B" DIN EN 60584-1:2014
IEC 60584-1:2013
ITS-90 0 to 1820 °C 0.15 % from 600 °C
W5Re-W26Re "C" DIN EN 60584-1:2014
IEC 60584-1:2013
ITS-90 0 to 2315 °C 0.1 % from 500 °C
W3Re-W25Re "D" ASTM E1751M-15 ITS-90 0 to 2315 °C 0.1 % from 500 °C
W5Re-W20Re "A1" GOST R 8.585-2001 ITS-90 0 to 2500 °C 0.1 % from 500 °C
Chromel®-Copel "L" GOST R 8.585-2001 ITS-90 -200 to +800 °C 0.1 % from -80°C
Chromel®-Alumel®
"K" GOST R 8.585-2001 ITS-90 -270 to +1372 °C 0.1 % from -80 °C
PLII (Platinel® II)
ASTM E1751M-15 ITS-90 0 to 1395 °C 0.1 %
Ambient temperature influence 100 ppm/K
Cold junction Internal (Pt100) or external (constant)
Cold junction accuracy (internal) ± 1K
Cold junction temperature (exter-
nal)
-30 to +85 °C (adjustable)
Base measuring range -20 to +70 mV