70652100T10Z001K000
RTD temperature probe
Resistance transmitter and resistance/potentiometer
Designation Standard ITS Measuring range Accuracy
a
a
Accuracy refers to the measuring range.
Measuring
current
Pt50 DIN EN 60751:2009
IEC 60751:2008
ITS-90 -200 to +850 °C 0.1 % 500 μA
Pt100 DIN EN 60751:2009
IEC 60751:2008
ITS-90 -200 to +850 °C 0.1 % 500 μA
Pt500 DIN EN 60751:2009
IEC 60751:2008
ITS-90 -200 to +850 °C 0.1 % 50 μA
Pt1000 DIN EN 60751:2009
IEC 60751:2008
ITS-90 -200 to +850 °C 0.1 % 50 μA
Pt100 JIS C 1604:1981 IPTS-68 -200 to +649 °C 0.1 % 500 μA
Pt50 GOST 6651-2009 A.2 ITS-90 -200 to +850 °C 0.1 % 500 μA
Pt100 GOST 6651-2009 A.2 ITS-90 -200 to +850 °C 0.1 % 500 μA
Cu50 GOST 6651-2009 A.3 ITS-90 -180 to +200 °C 0.4 % 500 μA
Cu100 GOST 6651-2009 A.3 ITS-90 -180 to +200 °C 0.4 % 500 μA
Ni100 DIN 43760 (1987) IPTS-68 -60 to +250 °C 0.2 % 500 μA
Ni100 GOST 6651-2009 A.5 ITS-90 -60 to +180 °C 0.2 % 500 μA
Connection type 2/3/4-wire
Ambient temperature influence 50 ppm/K
Sensor line resistance Max. 10 Ω per cable for two-wire circuit
Max. 30 Ω per cable for three/four-wire circuit
Designation Measuring range Accuracy
a
Measuring current
Resistance transmitter 0 to 4000 Ω≤0.1 % 50 μA
Resistance/potentiometer 0 to 400 Ω≤0.1 % 500 μA
0 to 4000 Ω≤0.1 % 50 μA
Ambient temperature influence 100 ppm/K
Connection type
Resistance transmitter Three-wire circuit
Resistance/potentiometer Two/three/four-wire circuit
Smallest measuring span 60 Ω
Sensor line resistance Max. 10 Ω per cable for two-wire and three-wire circuits
Resistance values Freely programmable within the limits, in increments of 0.1 Ω
a
Accuracy refers to the maximum measuring range. Small measuring spans lead to reduced linearization accuracy.