Installation Instructions User Manual

27
7 Technical data
Transducer short-circuit/break
Logic inputs (extra code)
Outputs
External analog inputs / logic inputs / logic outputs
Screen
Range start/end freely programmable within the limits in 0.1 mA steps
Sampling cycle 6 or 12 channels 125msec
Input filter 2nd order digital filter; filter constant adjustable from 0 to 10.0sec
Feature adjustable linearizations for thermocouples and resistance thermometers
(for connection of transmitters without linearization)
Short-circuit
1
Break
1
Thermocouple not detected detected
Resistance thermometer detected detected
Resistance transmitter detected detected
Potentiometer not detected detected
Voltage up to ± 1V not detected detected
Voltage > ± 1V not detected not detected
Current not detected not detected
1. programmable reaction of instrument, e.g. triggering alarm
Number 7 to DIN VDE 0411, Part 500;
max. 25Hz, max. 32V
Level logic “0“: -3 to +5V,
logic “1”: 12 to 30V
Sampling cycle minimum 1sec
1 relay (ex-factory) changeover, 3A, 230V AC
1
4 relays (extra code) make/break, 3A, 230V AC
1
1 open-collector output
(extra code)
max. 25V, max. 100mA
1 voltage output
(extra code)
24V DC, 50mA
1. with resistive load. SELV circuits and supply circuits must not be combined.
Type JUMO mTRON automation system
Sampling cycle 1sec
Technical data see Data Sheet:
70.4015 Relay module
70.4020 Analog input module
70.4030 Logic module
Configuration Project design software iTOOL (70.4090)
Resolution 320 x 240 pixels
Size 5.7"
Number of colors 27 colors