JUNO TYPE IC & TC RECESSED HOUSING INSTALLATION INSTRUCTIONS
3"
Step 1. Extend bar hangers
to fit between joists. Position fixture by
hammering Real-Nails
TM
into joists. Make
certain to vertically position bottom edge of
bar hanger feet slightly above the joist
bottom. (Fig. 3)
(Note: Bar hanger may be shortened to fit 12"
framing by breaking at score lines).
Step 2. Slide fixture along bar hangers into
desired location. Use locking screw or slot to
secure (Fig. 4).
Step 3. Follow steps 1-4 under
Electrical Connection.
Step 4. After installing drywall, if necessary,
adjust fixture for ceiling thickness by
loosening hex screws that attach the round
housing to the plaster frame (Fig. 3).
Note: When installing in drywall, cut a 4-1/2" (for
4" housings), 5-5/8” (for 5" housings) or 6
-
-7/8” (for
6” housings)
opening so that it will line up with installed can.
For sloped ceiling housings, use the provided oval
hole template.
WARNING: For your safety, read and understand instructions completely before starting installation. Before wiring to power supply, turn off electricity at the fuse or circuit breaker box.
NOTE: Juno recessed fixtures are designed to meet the latest NEC requirements and are listed in full compliance with UL1571, 1570 or 1598. Before attempting installation of any recessed lighting fixture, check your local electrical building
code. This code sets the wiring standards and installation requirements for your locality and should be understood before starting work. Use of non-Juno trims voids Juno warranty.
Juno Type IC fixtures are designed for direct
contact with insulating materials which are
approved for this application (Fig. 2). Blinking
light after installation indicates that improper
bulb or trim is being used.
Use Juno Air-Loc Gaskets or Air-Loc Rated
Trims with Juno IC housings for additional
energy savings and to comply with
Washington State and other energy codes.
*In Canada, when insulation is present, Type IC fixtures
must be used.
Installation into Joist Construction
Installation into Suspended Ceiling
Figure 5
1300 South Wolf Road (847) 827-9880
Des Plaines, IL 60017 www.junolightinggroup.com
Electrical Connection Instructions
Step 1. Provide electrical service accord-
ing to your local electrical code to the
wiring box located on the plaster frame.
Supply wire insulation must be rated for at
least 90°C.
Step 2. Remove wiring box cover. Remove
the appropriate knock-out(s)
to accommodate the type of electrical serv-
ice to be used/allowed by your local electri-
cal code (Fig. 8):
Metal Conduit. Remove appropriate round
knock-out(s) and connect conduit to wiring
box with proper connectors (not supplied.)
Non-Metallic Cable. Remove
appropriate knock-out(s) from top of wiring
box and insert cable, pushing it past the
cable grip. No other connector is required.
Step 3.
Standard J-Box: Connect supply wires to
fixture wires with proper size wire nuts
(not supplied), so as to cover all bare
current-carrying conductors (Fig. 9).
J-Box with Quick Connectors: Strip sup-
ply wire 3/8˝, insert each supply wire into
appropriate junction box connector.
Connect black fixture wire to hot, white fix-
ture wire to neutral
and green fixture
wire to ground
(Fig. 9).
Step 4. Place all
wiring and connec-
tions back in wiring
box and replace
cover.
Black
Lamp Socket
Thermal Protector
White
120V
Figure 9
Figure 8
Metal Conduit
Non-
Metallic
Cable
TYPE TC & PL for Non-Insulated Ceilings
Juno Type TC & PL fixtures are designed for
installations where housing and J-Box will not
come into contact with insulation. Insulation
must be spaced 3" away from the housing
and J-Box (Fig. 1)*. Blinking light after
installation indicates that improper bulb or
trim is being used or that fixture has been
improperly covered with insulation.
TYPE IC for Insulated Ceilings
Figure 2
Figure 1
Step 1. Locate center of proposed opening on
ceiling tile and cut a 4-1/2" (for 4" housings),
5-5/8" (for 5" housings) or 6-7/8" (for 6"
housings) opening. For sloped ceiling housings,
use the provided oval hole template.
Step 2. Place ceiling tile in
T-bar grid.
Step 3A. Strip supply wire 3/8”, insert each
supply wire into appropriate junction box con-
nector. Connect black fixture wire to hot, white
fixture wire to neutral and green fixture wire to
ground.
Step 3B. (Optional) Place G2405
T-bar clip (sold separately) onto
bar-hanger feet (Fig. 6).
Step 4. If using optional G2405
T-bar clips, place fixture into
position and snap T-bar clips
onto T-bars. Otherwise, rest fixture on T-bars
with notches in hanger bars over the tops of the
T-bars and secure with wire (Fig. 5)
Step 5. Follow Steps 1-4 under
Electrical Connection.
Figure 6
Figure 3
Trim Installation
Install trim using coil,
leaf, torsion, or push-in
springs as provided.
Remove socket paint
protector cover and
install proper lamp as
listed on housing label.
Figure 7
© Juno 2004 Printed in USA
Figure 4
Hex Screws
12/04 #P5050