User guide

50
Appendix C -- MCD-8000 Display Specifications
MCD 8000 Functional Specifications
Input Range: 0-10VDC or 0-20mA
Note: Kaman Special input module (PN 853727) allows either a
+/-5VDC or +/-10VDC input to the meter but changes it
to be a single ended input.
Sensitivity: 200 microvolts/count or 0.4microamps per count
Note: on units with the Kaman input module (PN 853727) with a
+/-10VDC input, the display will only have 400 microvolt
per count sensitivity.
Input Impedance: Voltage mode >=1 Megohm
Current mode 5 ohms
Note: on units with the Kaman input module (PN 853727) with a
+/-10VDC input, the display will have a 20k ohm input
impedance.
A/D read rate: 2 per second nominal
Power: 115VAC +/-10%, 50-60 Hz; 230 VAC +/-10%, 50-60Hz
switch selectable