AIR FLOW TRANSDUCER MODEL 6332/6332D Oper ation Manual Please read this manual carefully and understand the warnings described in this manual before operating the product. Keep this manual handy for ready reference KANOMAX J APAN, INC.
Thank you for purchasing a product of Kanomax, Inc. Please read this operation manual carefully and operate the instrument appropriately by following the instructions given in this manual.
Component List ■ Standar d Item Airflow Transducer Main Unit (Without Display) Airflow Transducer Main Unit (With Display) Model Remarks 6332 - 6332D - ■ Pr obe & Cable (Sold Separ ately) Item Air Velocity Probe Model 0962-00 0963-00 0964-01 0964-02 0965-00 0965-01 0965-03 Uni-directional Omni-directional (Needle) Omni-directional (Spherical) 1504-04 1504-05 1504-06 Mini-temperature-compensation-sensor integrated type Omni-directional (Spherical) Mini-temperature-compensation-sensor independent
Impor tant Safety Infor mation In this operation manual, warning types and classifications are defined as follows. [Classifications] Danger : To Pr event Ser ious Injur y or Death Warnings in this classification indicate danger that may result in serious injury or death if not observed. Caution: To Pr event Damage to the Pr oduct Warnings in this classification indicate risks of damage to the product that may void the product warranty if not observed.
Danger ○ Never br ing the pr obe close to a flammable gas atmospher e. Do not use near flammable gas --- The heated sensor may cause fire or explosion. ○ Never disassemble, modify or r epair the instr ument. Do not modify / disassemble --- Failure to observe the above may cause short circuit and malfunction. ○ Use the specified voltage for power supply. --- Unspecified voltage may cause electrical shock and fire.
Caution ○ Do not use or leave the instr ument in a high temper atur e/humidity envir onment, or in a dusty envir onment. The instr ument must also not be left under dir ect sunlight for a pr olonged per iod. Prohibited Installation --- The instrument may not function properly outside the specified temperature range of 5 to 40 degrees C. ○ Do not wipe the instr ument with a volatile solvent. Prohibition --- The body may deform or deteriorate. Use soft dry cloth to remove stains.
Table of Contents Names and Dimensions of Components...................................................... 1 System Configuration Example.................................................................... 5 Connecting the Probe Cable to the Main Unit ............................................. 6 Connecting the Probe Cable to the Probe..................................................... 6 Installing the Data ROM...............................................................................
Names and Dimensions of Components (1) Model 6332 View inside the Case Probe Cable Connector Output Changeover Switch Range Changeover Switch ROM Socket Output and Power Terminal Blocks 1
(2) Model 6332D View inside the Case Probe Cable Connector Display Substrate Output Changeover Switch Range Changeover Switch ROM Socket Output and Power Terminal Blocks 2
(3) Model 6332 View with the Case 4-φ4.
(4) Model 6332D View with the Case 4-φ4.
System Configuration Example Probe (Sold Separately) Probe Cable (Sold Separately) Display (Only for 6332D) AC Adapter (Optional) Output Cable (Not Provided) 5
Connecting the Probe Cable to the Main Unit - Make sure to cut the power supply to the main unit before connecting the probe cable (sold separately). The probe cable must be wired separately from the power line. Match the concave part of the main unit connector with the convex part of the cable connector (4-pin), and click them in (not a screw type).
Installing the Data ROM - Make sure to cut the power supply to the main unit before installing the Data ROM. Install the correct Data ROM that corresponds to the probe number. Position the Data ROM in the correct orientation. After confirming that the Data ROM is properly set, use the flat-blade screwdriver to rotate the cam 90 degrees clockwise to lock it in.
Switching Output (Setting Current/Voltage and Output Range) - Make sure to cut the power supply to the main unit before switching the current/voltage output. Output can be set by either voltage output (0 to 5V) or current output (4 to 20mA). (The factory default setting is provided with current output.) 1. Current / Voltage output can be switched by the DIP switch. 2.
Output Changeover DIP Switch Range Changeover Rotary Switch 9
Connecting Output and Power Supply - Pay attention to the polarity of power supply when connecting. Power supply voltage must be DC 12 to 24V. FG Terminal DC-IN Term. - DC-IN Term. + OUT Term. - OUT Term. + FG (*1) Power Supply Input (-) Power Supply Input (+) Signal Output (-) Signal Output (+) (*2) (*1) FG: Frame Ground -------- Connect to ground (earthing). (*2) NC: No Connection ------- Connection is not required.
Measurement Method 1. Using the Uni-directional Probe (Model 0962-00, 0963-00) These probes have directivity characteristics which require the direction mark to be faced against the airflow for measurement. When you are not sure of the airflow direction, slowly rotate the probe in the horizontal direction, and select the point where the air velocity reading is maximum. 2.
Optional Accessory 1. Display Unit (Model 6332-01) Number of digits and range of air velocity value to be shown on the display corresponds to the setting of the air velocity output range as shown below. No. Output Range [m/s] Display Range [m/s] 0 0 ~ 2.00 0.00 ~ 2.00 1 0 ~ 5.00 0.00 ~ 5.00 2 0 ~ 10.00 0.00 ~ 10.00 3 0 ~ 25.0 0.0 ~ 25.0 4~9 0 ~ 50.0 0.0 ~ 50.
2. AC Adapter (Model 6332-02) Do not connect the AC plug to the power receptacle before connecting the DC plug to the main unit. Failure to observe the above may cause short circuit and damage to the AC adapter. Observe the polarity and firmly insert the DC plug into the main unit as shown below. Then connect the AC plug to the power receptacle. * The one which is marked is minus. 1 DC-IN Term. - DC-IN Term.
Cleaning the Probe If any impurities such as dust, soot and oil are attached to the sensor, the amount of heat that the airflow draws from the sensor surface (heat dissipation rate) will change, thus the air velocity reading will be affected. The probe must be cleaned when the sensor is contaminated from use in an unclean environment. Cleaning Method Clean the sensor portion of the probe in an ultrasonic cleaner for approx. 10-20 sec.
Specification of Main Unit Product Name Airflow Transducer (with / without Display) Model 6332 / 6332D Measuring Object Clean Airflow Measuring Range Maximum range 0.1 ~ 50 m/s (Depending on the measurement range of the probe*) Measuring Accuracy Temperature Compensation Range Output Setting of Output Range Display (Optional) Power Supply Power Consumption (Reference Value) ± (3% of reading + 0.1) m/s 5~40℃ 0.1-4.99m/s 5.00-9.99m/s 10.0-24.9m/s 25.0-50.0m/s ±0.25m/s ±0.50m/s ±1.25m/s ±2.
Specification of Probes (Sold Separately) MODEL Measuring Range 0962-00 0963-00 0964-01 Uni-directional 0.1~50.0m/s Omni-directional (Needle) 0964-02 0965-00 0965-01 0.1~25.0m/s Omni-directional (Spherical) Mini-temperature-compensation-sensor integrated type Omni-directional (Spherical) 0965-03 0965-04 0965-07 Sensor Type 0.1~25.0m/s Mini-temperature-compensation-sensor independent type Omni-directional (Spherical) 0965-08 Air Velocity Sensor Air Velocity Sensor Temp.
Air Velocity Sensor Temp. Compensation Sensor Air Velocity Sensor Temp. Compensation Sensor Shielded Cable I-type L-type 00: protruding tip 01: no protrusion Air Velocity Sensor Temp.
Troubleshooting Please check the following list before requesting a repair: Symptom No Output Abnormal Output Possible Cause Solution (& Reference Page) The main unit is not turned on. Supply power to the main unit. (Page 10) Wrong wiring of the output terminal. Provide proper wiring. (Page 10) Probe is not connected properly. Turn off the power. Reconnect the probe to the main unit and turn the power back on. (Page 6) Contact of the terminal block is dirty.
Product Warranty and After Service Product Warranty A warranty card is not included in this product. This product is warranted against defects in materials and workmanship for a period of one year from the date of original purchase. After Service When you have a problem with your unit, please check out the “Troubleshooting” section (page 18) first. If that does not help, please contact your local distributor, or call our service center (See last page for contact information).
Contact Information JAPAN KANOMAX JAPAN, INC. 2-1 Shimizu Suita City, Osaka 565-0805, Japan TEL: 81-6-6877-0183 FAX: 81-6-6879-5570 URL: http://www.kanomax.co.jp/ E-Mail: sales@kanomax.co.jp USA & EUROPE KANOMAX USA, INC. PO Box 372, 219 Route 206, Andover, NJ 07821 U.S.A. TEL: (800)-247-8887 / (973)-786-6386 FAX: (973)-786-7586 URL: http://www.kanomax-usa.com/ E-Mail: info@kanomax-usa.com CHINA Shenyang Kano Scientific Instrument Co., Ltd No.