CAPTURE HOOD MODEL 6710 INSTRUCTION MANUAL Be sure to read this manual thoroughly before using the instrument. Fully understand and pay attention to each caution mentioned. Please keep this manual as a service reference.
Thank you for your purchasing a KANOMAX instrument. This is a precision instrument, please read this instruction manual carefully before using the instrument and pay attention to all the cautions under the instructions.
Composition & Parts Standard part: Model No.
ATTENTIONS & NOTES The warning symbols mentioned in this manual are defined below: 〔symbol classifications〕 Danger: To Prevent Serious Injury or Death Warnings in this classification indicate a danger that may result in serious injury or death if not observed. Caution: To Prevent Damage to the Product Warnings in this classification indicate a risk of damage to the product that may void the product warranty if not observed.
DANGER z Forbidden Do not exposure the instrument to rain or water. …… Otherwise, it may cause an electric shock, fire or injury. CAUTION z Always unplug the instrument when it is not in use. …… Failure to do so may cause an electric shock, fire or circuit damage. z Using properly …… Failure to do so may cause battery leakage and damage to the instrument. z Only use the provided AC adapter. ……Otherwise it may damage the instrument.
CONTENTS 1.Introduction ........................................................................................................................ 1 1.1 Product features ......................................................................................................... 1 2. Capture Hood Structure ....................................................................................................... 2 2.1 Capture Hood Base ..................................................................................
5.1.4 Actual flow, Standard flow settings ................................................................. 17 5.2 General settings ....................................................................................................... 18 5.3 Data processing settings .......................................................................................... 19 5.4 Communication settings ........................................................................................... 20 5.5 Print Settings .........
1.Introduction The model 6710 is used to measure the air flow at the supply and the exhaust points of an HVAC system. There are several interchangeable hoods of various sizes so it’s easy to find one that will match the size of the supply and exhaust points of any HVAC system. The standard size hood is 2ft×2ft (610mm×610mm). Four additional sizes are also available as options: 2ft×4ft (610mm×1220mm). 1ft×4ft (305mm×1220mm). 2ft×3ft (610mm×915mm). 3ft×3ft (915mm×915mm).
2. Capture Hood Structure The capture hood consists of a fabric hood, main structure and an instrument base. The structural drawing is below: Fabric hood Instrument base Main structure 2.1 Instrument Base 1) The exterior structure of the base as below: Portable handle 2)The internal structure of the base as below: Back pressure on/off Back pressure plate Base button Measurement matrix Main structure Test handle 3)Matrix There are sixteen measuring points for testing air flow.
2.2 Main structure Cover lock Keypad Display LCD Battery Compartment Cover Socket for communicatio Side view Back Front view POWER 2.3 Fabric Hood The fabric hood kit consists of a frame, and a fabric hood with four windows as shown below: Window Frame Fabric hood 3. Installation and Assembling 3.1 Capture Hood Installation 1)Assemble the fabric hood and the frame as shown below: ④ ③ ③ ① ② Use the angled corners ① and the stitching ② as a guide to ensure the hood is straight.
2)The figures below are provided as a reference. a. Use the mark ① and the stitching as a guide to ensure the hood position. b. Make sure the hood fully wraps around the base. ① 3.2 Assembling the Frame (detail) Insert one end of a support pole into its pole mount in the base as in figure ① and the other end into the frame corner as in figure ②. For the positions of the remaining 3 poles refer to figure ③, and repeat the steps as above.
3.4 Installing the Main structure To install the Main structure ①, set the bottom of the panel in the holder on the unit base ② and gently push the top of the panel backwards ③ until it locks into place. To remove it, simply reverse the procedure. ③ ② ① 4. Operation directions 4.1 Communication and Supplying Power with the AC Adapter Connect the main structure to a PC (refer to figure ①). ① The main structure is connected to a PC.
4.2 Supplying Power with Batteries ¾ 4 AA-size batteries can be used for a power supply. ¾ Press the compartment cover lock (refer to figure ①), and then slide the cover off to open the battery compartment. ¾ Put 4 AA-size batteries in and make certain the batteries are correctly oriented. ¾ New alkaline battery or rechargeable Ni-MH battery can be used. Never mix battery types, or ¾ battery leakage or damage to the instrument may occur. Replace the compartment cover (refer to figure ②).
4.3 ON/OFF 1. Getting started The LCD is displayed below for reference: (1)Press【POWER】for a while. (2)Then you enter into the main interface as shown in the left figure. 2. Shut down Press and hold 【POWER】for more than 2 seconds in any mode, and the instrument will turn off automatically. 4.4 Keypad Operation Keypad operations include the keypad on the control panel as well as the switches on the base. The keypad on the control panel is shown below.
z SAVE: Save the current test results. z SET: Store changes or enter into the selected option’s next level interface. z MENU: On the main screen holding this down for 2 seconds will enter into the main “MENU”. z OK: Pressing for 2 seconds will save the date or time in the “General Settings”, Pressing for 2 seconds will delete saved data in the “Record Processing”. z START: Begin a measurement in main menu. z STOP: Stop a measurement in main menu.
Right switch makes the panel tilt up. Left switch makes the panel tilt down. Note: 1. The instrument may turn off, when you attempt to adjust the incline settings of the instrument if the battery display is at . 2. You can’t adjust the incline settings of the instrument when testing or if you’re not in the main interface. 3. To conserve power,avoid tilting the screen unless necessary. 4.
4.7 Measuring 4.7.1 Start and enter into the main interface To start measuring, go to the main interface menu as shown below: h a b g f 2012 / 06 / 01 13 : 10 : 10 Cycle : 050 Test Mode: Test ID : 13 e Single ---- m³/h SAVE d START c 25.4 ℃ 53.4 %RH MENU a. Test ID, Cycle——save the testing No. in Cycle and the corresponding Test ID. b. Air flow display ——display the testing data of air flow. c. Temperature, Humidity ——display the current temperature and humidity in real time.
1)“Single” measurements are individual flow measurements. When you press “START”, the instrument will begin measuring and the air flow value will be displayed as “- - - -”. 2)The test will stop automatically when the air flow is stable and a flow value with the corresponding wind direction will be displayed. Air flow will be stable within 8 seconds. The greater the air flow the shorter the time needed to stabilize.
4.7.4 Back Pressure Compensation Measurement Mode When measuring air flow in an environment with a strong wind or turbulent flow, it will produce resistance for test air flow and system pressure. It is suggested you turn the Back Pressure Compensation ON when the air flow is more than 1500 m3/h, otherwise you can test without the Back Pressure Compensation ON. 1) When “B. Press” mode is turned on, press “START” and the measurement will begin.
5.1 Test Settings MENU (1)Press 1 1.Test Settings 2. General Settings or to select “Test Settings”, and press to MOVE 3. Record Processing 4. Communication SET 5. Print OK EXIT enter into “Test Settings”. Press return to the main interface. (2) The option items in “Test Settings” are as follows: 1. Test ID Test Settings 1. 1 Test ID 2. Test Mode Single 3. Unit 4. Act.Std Std 2. Test Mode MOVE SET OK 3. Unit 4. Act.
5.1.1 Test ID setting A Test ID consists of a group of Cycles (or Samples). A Test ID can contain up to 100 Cycles. The maximum number of Test IDs is 30. Any new Sample will be saved to the current Test ID. You can change the current Test ID at any time to keep your data organized. Press to return to the “MENU” and the settings will not be saved. Refer to the figures as below: Test Settings 1. 1 Test ID 2. Test Mode Single 3. Unit 4. Act.
5.1.2 Test Mode settings This setting is for change the test mode & the settings about the test modes. Refer to the steps below: Test Settings ¾ Under “Test Settings”, press 1. Test ID 2 Test Mode 2. Single 3. Unit 4. Act.Std MOVE or to select 2 “Test Mode”. SET Std ¾ Press to enter into the “Test Mode” setting. BACK ¾ Press to return to “MENU”. MOVE ¾ Press or OK Test Settings 1. Test ID 2. Test Mode Single 3. Unit RunAvg B.Press 4. Act.
5.1.3 Set Units of Measure for Airflow, Temperature and Atmos For available units, refer to the below chart: Display shows Available units Air flow m³/h, CFM, l/s Temperature ℃, ℉ Atmos kPa, inHg To change the units of measure, follow these steps: Test Settings ¾ Under “Test Settings”, select the option 3 “Unit”. 1. Test ID 2. Test Mode 3 Unit 3. 4. Act.Std Single MOVE Std SET ¾ Press enter to the “Unit” settings or press to return to “MENU”. OK BACK Unit 1 Airflow 1. CFM 2.
5.1.4 Actual flow, Standard flow settings This setting is for selecting Actual air flow [ACT] or Standard air flow [STD]. Test Settings 1. Test ID 2. Test Mode Single 3. Unit 4. Act.Std MOVE SET Std ¾ Under the “Test Settings”, select option 4 “Act. Std”. ¾ Press to enter or press to return to “MENU”. OK BACK Test Settings 1. Test ID 2. Test Mode Single 3. Unit 4. Act.Std MOVE SET Act Std OK ¾ Press or ¾ Press to change the settings as shown below.
5.2 General Settings ¾ Under “MENU”, select option 2 “General Settings”. MENU 1.Test Settings 2 General Settings 2. MOVE ¾ Press to enter “General Settings” or press to 3. Record Processing 4. Communication return to the main interface. SET 5. Print OK EXIT ¾ The settings includes: Date, Time, Backlight and Auto General Settings 11. Data 2012 / 06 / 01 2. Time 13 : 10 : 10 3. Backlight High 4. Auto Shut Off Shut. MOVE SET OK BACK Under option 1, press General Settings 1.
5.3 Data processing settings MENU 1.Test Setting 2. General Settings MOVE ¾ Under “MENU” select option 3 “Record Processing”. 33. Record Processing 4. Communication SET 5. Print ¾ Press OK to to select “Record Processing”. Press return to the main interface. EXIT Record Processing 11.Display MOVE 2. Delete SET OK ¾ Press or ¾ Press to select a setting to change, or press Under option 1, press Max: Min: Avg: T: H: Time: .
Under option 1, press Detele No Yes No 1. Delete All 2. Delete IDs Select ID: 05 3. Delete Cycles ¾ Press ADJ No or ¾ Press SET Select ID :12 Select Cycle:000 . t OK to select option item as below. for 2 seconds to save the changes or press to quit. No Yes BACK Under option 2, press . Detele 1. Delete All 2. Delete IDs No Select ID: 05 3. Delete Cycles No ADJ ¾ Press SET Select ID :12 Select Cycle:000 No or to save the changes or press ¾ Press OK to select ID No. to quit.
5.5 Print Settings Note:Before printing ensure the following: 1. Please select the factory configuration printer and printer cable. For details, refer to the printer manual <>. 2. Baud Rate is set to 19200. The initial value is set to 19200. MENU 1.Test Setting 2. General Settings ¾ Under “MENU”, select option 5 “Print”. MOVE 3. Record Processing 4. Communication 5 Print 5. SET OK ¾ Press to select “Print” or press return to the main interface. EXIT Print 12.
Under option 1, press Print By IDs ADJ Start ID: Stop ID: Print: 05 No SET Total ID: 05 OK 01 . ¾ Press or to select the “Start ID” value. ¾ Press to save or press ¾ Press or ¾ Press to save or press ¾ Press or to quit. BACK Print By IDs to select the “Stop ID” value. ADJ Start ID: Stop ID: Print: 05 No SET Total ID: 05 OK 01 to quit. BACK Print By IDs Start ID: Stop ID: Print: Total ID: ADJ 01 05 No Yes SET 05 OK to select option item as below.
6.Main Specifications Items Flow range 40~4300 m³/h Accuracy Readings ±3%± 10 m³/h(Air Flow >85 m³/h) Resolution 1 m³/h Temperature range 0~60℃ Accuracy ±0.5℃(within 5~40℃±0.3℃) Resolution 0.1℃ Humidity range 0~100%RH Accuracy ±3%RH(10~90%RH) Resolution 0.1%RH Air Flow Temperature 6710 Humidity Operating Temperature range 0~60℃(no condensing) Storage Temperature range -20~70℃(no condensing) Atmos.
7. Common Trouble Shooting Symptom Possible causes / troubleshooting Check the positive/negative connections of the batteries. →Verify the batteries are inserted correctly. No display Low battery charge. →Replace or recharge the batteries. Low battery charge. →Replace or recharge the batteries. Main structure cannot be adjusted A test is running. →Stop the test, adjust the incline settings of the instrument again. Check the interface. →Return to the main interface. “DATA Error” after test in B.
8. Warranty and After-service 8.1 Warranty Seller warrants the goods sold hereunder, under normal use and service as described in the operator’s manual, shall be free from defects for a period of one year from the date of shipment to the customer. 8.2 After-service Check the “Common Trouble Shooting” table and see if your problem is listed there. If other problems occur, please contact the factory (see the last page for contact information).
□CHINA SHENYANG KANO SCIENTIFIC INSTRUMENT CO., LTD. #2610, 51 Wulihe Street, Heping District, Shenyang PRC. TEL: 024-23846440 83951688 83951788 FAX: 024-23898417-820 URL:http://www.kanomax.com.cn KANOMAX INSTRUMENT(SHENYANG), INC. #9, Zheng kun Road, Shenbei New District, Shenyang, PRC. TEL: 024-89730178 FAX: 024-89730177 □USA KANOMAX USA, INC. P.O. Box 372 219 U.S. Highway 206, Andover, New Jersey 07821 U.S.A. TEL: (800)-247-8887 / International +1(973)-786-6386 FAX: +1(973)-786-7586 URL: http://www.