5. From the Serial Port dropdowns, select an LPM port for each RF channel to use to communicate with the
LC. By default, RF Channel 1 communicates with the LC via LPM COM 1, RF Channel 2 communicates
with the LC via LPM COM 2 and so on up to RF Channel 8.
Note: More than one RF Channel can communicate via one LPM COM port, if necessary.
6. Click the Serial tab on the Configuration page.
Result: The following screen appears.
7. Ensure all the COM Ports selected in step 5 are enabled by selecting the corresponding Serial Port
State check box.
8. Select the Baud Rate, Data Bits, Parity, and Stop Bits to match the LC communication settings.
9. Press Enter to accept the configuration.