3.2 Requirements for the Installation Location
3.2.1 General
Install the K-BOW system indoors only and as a stationary system in weather-protected
and temperature-controlled locations.
Comply with the permissible ambient conditions stated in the data sheets of the K-BOW
components.
Ensure that only authorised personnel are allowed access to the installation location(s) of
the system rack (main rack and extension racks).
3.2.2 Rack Installation
The installation location of the rack for the C- and E-hub must
be indoor,
be larger than 1000 × 800 × 2500 mm,
be at least 200 mm away from the wall.
provide a clearance of at least 3 HU of height above and below any C-hub or E-hub
( in Fig. 4),
provide sliding rails for weight unloading.
A
A
Fig. 4: Clearance above radiation ns of
the installed devices
B
Fig. 5: Sliding rails