Preconditions and Requirements
936.5467 0.92
3.2.3 Wall Installation
The static loading calculations must ensure that a rack up to 500kg in weight can be
erected and operated.
The permissible ambient temperature range of the system is –5 to +55°C (ambient air).
1)
If required, install active cooling (air conditioning) to ensure the permissible ambient
temperature of the system is satis ed.
The safety clearance between adjoining systems must be complied with. See the
speci cations of the companies operating the adjoining systems.
If you use racks other than those recommended by Kathrein, make sure that the
following conditions are satis ed:
All height units not used must be blanked off.
The door must permit the passage of air over its entire surface, for instance by
perforation.
The cooling air must  ow through the rack from the front between the K-BOW
components, upwards and to the back where it is exhausted.
The cooling air fans at the top of the rack must be capable of a throughput of
≥960m
3
/h unimpeded air  ow.
1)
The permissible ambient temperature range applies to the racks recommended by Kathrein.
These racks ensure optimum dissipation of heat.