Cut Sheet

D
ATA SHEET D-810
KBAC SERIES
ADJUSTABLE FREQUENCY DRIVES
For 3-Phase AC Motors
NEMA-4X / IP-65
Models KBAC-24D, 27D, 29, 45, 48
W
ashdown and Watertight for Indoor and Outdoor Use
Rated for 208-230 and 400/460 Volt 50 & 60 Hz
3
-Phase AC Induction Motors from Subfractional thru 5 HP
Operates from 115, 208/230, and 400/460 Volt 50/60 Hz AC Line
TYPICAL APPLICATIONS
Conveyors • Packaging Equipment • Door & Gate Openers
HVAC • Indexers • Portable Equipment used with GFCIs
1
STANDARD FEATURES
Industrial Duty Die-Cast Aluminum Case with Hinged Cover A
vailable
i
n black finish or FDA approved white finish.
S
imple to Operate
Does not require programming. Uses trimpots and
jumpers, which are factory set for most applications.
Motor HP Selection Jumper Allows the drive to be used on a wide range
of motor horsepower without recalibration.
Diagnostic LEDs Power on (POWER) and drive status (STATUS).
Run/Fault Relay Output Contacts Can be used to turn on or off equip-
ment or to signal a warning if the drive is put into the Stop Mode or a fault
has occurred.
Start/Stop Switch Pr
ovides electronic start and stop functions.
Barrier Terminal Block Facilitates wiring of motor, AC line, and Run/Fault
Relay Output Contacts.
Jumper Selection of Drive Output Frequency – Increases the motor
speed up to two times the rated RPM.
Compatible with GFCIs (with optional software).
PERFORMANCE FEATURES
Power Start™ Provides more than 200% starting torque which ensures
startup of high frictional loads.
Slip Compensation with Static Auto-Tune and Boost Provides excellent
load regulation over a wide speed range.
Speed Range 60:1
PROTECTION FEATURES
Motor Overload (I
2
t) with RMS Current Limit Provides motor overload
pr
otection which pr
events motor burnout and eliminates nuisance trips.
2
Electronic Inrush Current Limit (EICL™) Eliminates harmful inrush AC line
curr
ent during startup.
Short Circuit Shuts down the drive if a short circuit occurs at the motor
(phase-to-phase).
Regeneration Eliminates tripping due to bus overvoltage caused by rapid
deceleration of high inertial loads.
Undervoltage and Overvoltage Shuts down the drive if the AC line input
voltage goes above or below the operating range.
MOV Input T
ransient Suppr
ession.
Microcontroller Self Monitoring and Auto-Reboot.
TRIMPOT ADJUSTMENTS
Minimum Speed (MIN) Maximum Speed (MAX)
Acceleration (ACC) Deceleration (DECEL)
3
Slip Compensation (COMP) Slip Compensation (COMP)
Boost (BOOST) Jog (JOG)
* Requires CE approved RFI Filter. See AC Line Filters, in Optional Accessories.
Notes:
1.
Requires optional software. 2. UL a
pproved as an electronic overload protector f
or motors.
3. When the drive is set f
or DC Injection Braking,
The DECEL Trimpot is used to adjust the braking intensity and time.
DESCRIPTION
The KBAC Adjustable Fr
equency Drives are variable speed controls
housed in a NEMA-4X / IP-65 washdown and watertight enclosure. They are
designed to operate 208-230 and 400/460 Volt 50 & 60 Hz 3-phase AC induc-
tion motors from subfractional thru 5 HP. The sine wave coded Pulse Width
M
odulated (PWM) output operates at a carrier frequency of 16 kHz which pro-
vides high motor efficiency and low noise. Adjustable Linear Acceleration and
D
eceleration make the drive suitable for soft-start applications.
Due to its user-friendly design, the KBAC is easy to install and operate.
Tailoring to specific applications is accomplished with selectable jumpers and
t
rimpots, which eliminate the computer-like programming required on other
drives. However, for most applications no adjustments are necessary. For more
advanced programming, PC based Drive-Link™ software is available.
Main features include adjustable RMS Current Limit and I
2
t Motor Overload
Protection.
2
In addition, Adjustable Slip Compensation with Static Auto-Tune and
Boost provides high torque and excellent load regulation over a wide speed
range. Power Start™ delivers over 200% motor torque to ensure startup of high
frictional loads. Electronic Inrush Current Limit (EICL™) eliminates harmful AC line
inrush current. A Run/Fault Relay is provided, which can be used to turn on or
off equipment or to signal a warning if the drive is put into the Stop Mode or a
fault has occurred. The drive is suitable for machine or variable torque (HVAC)
applications. Also, a jumper is provided for selection of Regenerative or DC
Injection Braking.
Standard front panel features include diagnostic LEDs for power on and
drive status, a Start/Stop Switch, and a Main Speed Potentiometer. Other fea-
tures include a Barrier Terminal Block to facilitate wiring of the AC line and motor,
adjustable trimpots (MIN, MAX, ACCEL, DECEL, COMP
, CL, JOG, BOOST), cus-
tomer selectable jumpers (Line V
oltage (dual voltage models only), Motor
Horsepower, Automatic or Manual Start/Reset, Motor Frequency, Frequency
Multiplier
, Fixed/Adjustable Boost, Regenerative/Injection Braking, “Run” or
“Fault” Output Relay Operation, NO/NC Stop Contact, Constant/Variable Torque,
Factory Assignable Function).
Optional accessories include: Forward-Stop-Reverse Switch, On/Off AC
Line Switch, Run-Stop-Jog Switch, Signal Isolator, Auto/Manual Switch, Class
“A” AC Line Filter, Multi-Speed Board, Programming Kit, Modbus Communi-
cation Module, and Liquidtight Fittings. A connector is pr
ovided for easy installa
-
tion of accessories.
A Complete Line of Motor Drives
*
KBAC-48
P/N 9540 (black)
P/N 9541 (white)
KBAC-24D
P/N 9987 (black)
P/N 9988 (white)

Summary of content (4 pages)