TABLE 1. FIELD CONNECTIONS (SHUNT-WOUND MOTORS ONLY)
AC LINE
VOLTAGE
FIELD VOLTAGE
(VDC)
FIELD
CONNECTION
FIELD TYPE
115 100 F+, F- Full Voltage
115 50 F+, L1 Half Voltage
230 200 F+, F- Full Voltage
CAUTION
Shunt-wound motors may be
damaged if field remains energized
with the motor stopped for an
extended period of time, unless
provided with external cooling.
230 100 F+, L1 Half Voltage
TABLE 2. ELECTRICAL RATINGS
RATING WITHOUT
AUXILLARY HEAT SINK
RATING WITH
AUXILLARY HEAT SINK
Model
No.
Part
No.
AC
Line
Voltage
(VAC)
+/- 15%
50/60
Hz
Motor
Voltage
(VDC)
(3)
Max.
AC
Load
Current
(RMS
Amps)
Max.
DC
Load
Current
(Avg.
Amps)
Max.
HP
Max.
AC
Load
Current
(RMS
Amps)
Max.
DC
Load
Current
(Avg.
Amps)
Max.
HP
Field
Voltage
(Shunt
Wound
Motor
Only)
(VDC)
KBIC-
120
9429 115 0 – 90 9.0 6.0 0.5 18.0 12.0 1 50, 100
KBIC-
125
9433 115 0 – 90 12.0 8.0 0.75 24.0 16.0 1.5 50, 100
KBIC-
240
9428 208/230 0 – 180 9.0 6.0 1 18.0 12.0 2 100, 200
KBIC-
225
9432 208/230 0 – 180 12.0 8.0 1.5 24.0 16.0 3 100, 200
115 0 – 90 0.5 1 50, 100
KBIC-
240D
(1)
9464
208/230 0 180
9.0 6.0
1
18.0
12.0
2 100, 200
KBIC-
240DS
(2)
9423 115,
208/230
0 – 90 9.0 6.0 0.5 18.0 12.0 1 100
Notes: (1) Model KBIC-240D is designed to accept 115 or 230 VAC line input to provide 0 - 130 VDC with a 115
or 230 VAC line and 0 - 220 VDC with a 208/230 VAC line. (2) Model KBIC-240DS is designed to accept 115 or
208/230 VAC line input to provide 0-130 VDC with a 115 or 208/230 VAC line. (3) A higher output voltage can
be reached by increasing MAX trimpot setting.