Connecting the mains supply line (example)
Connecting the mains supply line
► Shorten the connection wires to the
appropriate length; these should be kept
as short as possible.
The PE conductor must be longer than
the remaining conductors!
► Strip approx.12 mm from the connection
wires.
Wire end sleeves are recommended for
finely stranded wires.
► Perform the connection of the mains
supply line [L1], [L2], [L3], [N] and [PE].
Observe which phase conductor you
connect to terminal [L1] if several
charging stations are installed in a
network (DIP-switch settings for load
management).
1-phase connection
It is also possible to perform a 1-phase connec-
tion of the charging station. Use the terminals
[L1],[N] and [PE].
Supply terminals
Supply terminals
The supply terminals are designed as spring-
type terminals.
► Insert the flathead screwdriver (blade with
5.5 mm) into the supply terminal as
shown on the picture.
Terminal data:
- inflexible (min.-max): 0.2 – 16 mm²
- flexible (min.-max): 0.2 – 16 mm²
- AWG (min.-max): 24 – 6
- flexible (min.-max) with wire end sleeve:
Without/with plastic sleeve
0.25 – 10 / 0.25 – 10 mm²
- Stripping length: 12 mm
- Flathead screwdriver: 5.5 mm