User manual

Installation
28 / 48
4.4.3 Enable input [X1] (except e-series)
The enable input is equipped for the use with a potential-free contact. Using the enable input, it is
possible to control the charging station using external components (e.g. external key switches,
ripple control receiver of the energy supplier, house control, time switches, combination lock, pho-
tovoltaic system etc.).
Circuit diagram:
Electrical requirements:
Ensure a safe separation from dangerous voltages for this control cable outside of the device.
Logical function:
Enable contact
State of the charging station
Open
LOCKED
Closed
READY FOR OPERATION
Connection:
Connect the wires to the enable input (please refer to the "Terminals [X1/X2]" chapter for
details about the terminal).
DIP-switch setting
DIP-switch setting
The use of the enable input must be activated
by a DIP-switch setting.
Using the enable input:
- "Yes": DSW1.1 = ON
- "No": DSW1.1 = OFF (Default)