User manual

Installation
30 / 48
Example (supplement to the circuit diagram):
The switch contact can be used to switch off the KeContact P20 (disconnect the current) by
means of an overriding disconnect solution.
-Q1… Main circuit breaker
-Q2… Line circuit breaker + RCD circuit breaker
-Q3… Contactor/Relay
-F1… Current-limiting protective device
-U1… Undervoltage release
-X2… Switch contact output
4.4.5 Terminals [X1/X2] (except e-series)
Terminal
Terminals
The terminals for the enable input [X1] and the
switch contact output [X2] are designed as
spring-type terminals.
Terminal data:
- Cross-section (min.-max): 0.08 4 mm²
- AWG (min.-max): 28 12
- Stripping length: 8 mm
- Flathead screwdriver: 3,0 mm