Connecting the power supply line
Shorten the connection wires to the appropriate
length; these should be kept as short as possible.
The PE conductor must be longer than the remain-
ing conductors!
Strip approx.12mm from the connection wires.
Core-end sleeves are recommended for fine
stranded wires.
Carry out the connection of the power supply line
[L1], [L2], [L3], [N] and [PE].
Observe which phase conductor you connect to ter-
minal [L1] if several charging stations are installed
in a network (DIP switch settings for load manage-
ment).
1-phase connection
It is also possible to connect the charging station with
only 1-phase; the terminals [L1], [N] and [PE] are to be
used for this.
Supply terminals…
The supply terminals are designed as spring-type ter-
minals.
Insert the flathead screwdriver (5.5 mm) into the
power supply terminal as shown in the figure.
Terminal data:
- Fixed (min.-max): 0.2 – 16 mm²
- Flexible (min.-max): 0.2 – 16 mm²
- AWG (min.-max): 24 – 6
- Flexible (min.-max) with wire end sleeve:
Without/with plastic sleeve
0.25 – 10 / 0.25 – 10 mm²
- Insulation stripping length: 12 mm
- Flathead screwdriver 5.5 mm
ATTENTION
Risk of breaking the terminal!
Do not press the screwdriver up, down or to the side!