User manual

Installation
33/44
USE FIXED IP ADDRESS (*2)
DSW2.1 to DSW2.4 / DSW2.5=OFF / DSW2.6=ON
Since multiple charging stations are located in a network; the charging
stations must be addressed.
Addressing is done using the DIP switches DSW2.1 to DSW2.4.
The settable Ethernet addresses start at 10 + DIP switch setting.
With 4-bit addressing, the addresses 11 to 26 can be used
[192.168.25.xx].
DSW2.1 = Address bit 2
0
(value=1)
DSW2.2 = Address bit 2
1
(value=2)
DSW2.3 = Address bit 2
2
(value=4)
DSW2.4 = Address bit 2
3
(value=8)
Example for address "17":
DSW2.1 = ON (Value=1)
DSW2.2 = ON (Value=2)
DSW2.3 = ON (Value=4)
DSW2.4 = OFF (Value=0)
Address= 10 + 1 + 2 + 4 + 0 = 17
(*2) Not valid for P30 x-series
CONNECTION TO HIGHER-RANKING COMMUNICATION MODULE
DSW2.1 to DSW2.4=OFF / DSW2.5=ON / DSW2.6=OFF
Activate communication hub mode.
Required for OCPP connection of a KeCon-
tact P30 x-series or a KeContact C10 com-
munication hub.
D2.5 ON= yes
PLC MODEM (DSW2.7)
Deactivate PLC modem D2.7 ON= yes
COMMISSIONING MODE (DSW2.8)
Activating the commissioning mode
(for details, see Chapter " 4.7.1 Commis-
sioning mode/self test [34]").
D2.8 ON= yes
Set D2.1 to D2.7 to OFF!
en