Dimensions Guide

4
SPECIFICATIONS
Model Number B6BMM
X24K-A X30K-A X24K-B X30K-B X36K-B X42K-B X48K-C X60K-C
Nominalcooling
capacity-BTUh
1
24000 30000 24000 30000 36000 42000 48000 60000
Oricesize
TXV TXV TXV TXV TXV TXV TXV TXV
MaximumAvailable
AuxilaryHeat
15 15 20 20 20 20 30 30
NominalBlowerSize
(Dia.xWidth)
10x6 10x6 10x8 10x8 10x8 10x8 10x10 11x10
MotorHp-speeds-type
1/5-3-PSC 1/2-3-PSC 1/5-3-PSC 1/3-3-PSC 1/3-3-PSC 1/3-3-PSC 1/2-3-PSC
3/4-16-
BDC
FilterSize
(suppliedinternal
lterrack)
2
12x20x1 12x20x1 18x20x1 18x20x1 18x20x1 18x20x1 20x20x1 20x20x1
ApproximateShipping
Weight,lbs
87 90 107 110 110 130 150 155
Height,“H”,in.
43-5/16 43-5/16 43-5/16 43-5/16 49-5/16 49-5/16 55-15/16 55-15/16
Width,“W”,in.
14-3/16 14-3/16 19-11/16 19-11/16 19-11/16 19-11/16 22-7/16 22-7/16
SupplyAirOutlet
Dimension,in.
12-7/8x
12-3/4
12-7/8x
12-3/4
12-7/8x
18-1/4
12-7/8x
18-1/4
12-7/8x
18-1/4
12-7/8x
18-1/4
12-7/8x2112-7/8x21
Ref.ConnectionSizes,
in.(suc./liq.)
3/4-3/8 3/4-3/8 3/4-3/8 3/4-3/8 3/4-3/8 7/8-3/8 7/8-3/8 7/8-3/8
1
SeecurrentAHRIDirectoryforcertiedcombinationsandratings.
2
Filterisnotsuppliedwithunit.