Installation guide

Circuit Diagram
Note:
Conductor of at least 0.75mm 2shall be used for
wiring of defrost and evaporator fan control
load.
Conductor of at least 1.0mm 2shall be used for
wiring of compressor control load.
The inrush current for compressor may be 20A
instead of 8A during the 1 second period at the
start.
Notes for Installation
Before wiring, please read the instructions
carefully and be sure to understand the
function of every contact so that you can
make correct wire connections. Control
loads cannot exceed the ratings.
The temperature controller cannot be
installed in an area where water flows, a
dirty area, an area of high moisture, or in an
area with high temperatures. Please pay
attention to EMC problems and prevent the
temperature controller from collisions with
other objects.
The sensor cable leads must be kept away
from the main supply in order to avoid high
frequency noise. 0.75-1.5mm 2 flexible cords
should be used for wiring control load
terminals.
The evaporator sensor must be installed
between the fins of the evaporator in the
area where ice is the thickest. Do not place
the evaporator sensor near the electric
heater.
If the temperature controller is disturbed,
please cut off the power supply and reset.
The software of this product belongs to
grade A, and it does not apply to safe
control.
Please don't dismantle the controller. If you
need repairing or you have any problems in
using the controller, please do not hesitate
to contact our company.