Installation guide

GAS
COOKTOP
INSTALLATION
INSTRUCTIONS
TNIV
Tie
The
supply
line
must
be
equipped
with
an
approved
manual
shutoff
valve.
This
valve
should
be
located
in
the
same
room
as
the
cooktop
and
should
be
in
a
location
that
allows
ease
of
opening
and
closing.
DO
NOT
block
access
to
the
shutoff
valve.
The
valve
is
for
turning
on
or
shutting
off
gas
to
the
appliance.
Shutoff
Valve
-
Open
position
Figure
23
SHUTOFF
VALVE
Once
regulator
is
in
place,
open
the
shutoff
valve
in
the
gas
supply
line.
Wait
a
few
minutes
for
gas
to
move
through
the
gas
line.
FEAT
Check
for
leaks.
After
connecting
the
cooktop
to
the
gas
supply,
check
the
system
for
leaks
with
a
manometer.
If
a
manometer
is
not
available,
turn
on
the
gas
supply
and
use
a
liquid
leak
detector
(or
soap
and
water)
at
all
joints
and
connections
to
check
for
leaks.
A
WARNING
DO
NOT
use
a
flame
to
check
for
leaks
from
gas
connections.
Checking
for
leaks
with
a
flame
may
result
in
a
fire
or
explosion.
18.2,
Tighten
all
connections
if
necessary
to
prevent
gas
leakage
in
the
cooktop
or
supply
line.
Disconnect
this
cooktop
and
its
individual
manual
shutoff
valve
from
the
gas
supply
piping
system
during
any
pressure
testing
of
that
system
at
test
pressures
greater
than
1/2
psig
(3.5
kPa
or
14"water
column).
EZ]
Isolate
the
cooktop
from
the
gas
supply
piping
system
by
closing
its
individual
manual
shutoff
valve
during
any
pressure
testing
of
the
gas
supply
piping
system
at
test
pressures
equal
to
or
less
than
1/2
psig
(3.5
kPa
or
14”
water
column).
YW
©
Electrical
Requirements
120
volt,
60
Hertz,
properly
grounded
branch
circuit
protected
by
a
15
amp
circuit
breaker
or
time
delay
fuse.
DO
NOT
use an
extension
cord
with
this
cooktop.
cx
Grounding
Instructions
IMPORTANT
Please
read
carefully.
For
personal
safety,
this
appliance
must
be
properly
grounded.
The
power
cord
of this
appliance
is
equipped
with
a
3-prong
(grounding)
plug
which
mates
with
a
standard
3-prong
grounding
wall
receptacle
(see
Figure
25)
to
minimize
the
possibility
of
electric
shock
hazard
from
the
appliance.
The
wall
receptacle
and
circuit
should
be
checked
by
a
qualified
electrician
to
make
sure
the
receptacle
is
properly
grounded.
Where
a
standard
2-prong
wall
receptacle
is
installed,
it
is
the
personal
responsibility
and
obligation
of
the
consumer
to
have
it
replaced
by
a
properly
grounded
3-prong
wall
receptacle.
Preferred
Method
DO
NOT,
under
any
circumstances,
cut,
remove,
or
bypass
the
grounding
prong.
Grounding
type
wall
receptacle
Power
supply
cord
with
3-prong
grounding
plug.
Figure
24
POWER
SUPPLY
CORD
DO
NOT,
under
any
circumstances,
cut
or
remove
the
third
(ground)
prong
from
the
power
cord.
7
WESITIN
3)
Disconnect
electrical
supply
cord
from
wall
receptacle
before
servicing
cooktop.