DO NOT ground to a gas suppty pipe,
DO NOT connect to electrka! power suppJy until
appliance is permanendy grounded. Connect the
ground wire before turning on the power.
Where local codes permit connecting the appJiance-
grounding conductor to the neutral (white) wire
(see figure 3):
1. Disconnect the power supply.
2. In the circuit breaker, fuse box or junction box,
connect appliance and power supply cable wires as
shown in figure 3.
Cable from Power Supply
Cable from
appliance
Figure 3 - S-WIRE GROUNDED JUNCTtON BOX
You may not ground the cooktop
through the neutral (white} wire if cooktop is used
in a new branch circuit installation (!995 NEC),
mobile home, recreational vehicle, or where beat
codes do not permit grounding to the neutraJ
(white) wire. When grounding to the neutral
(white} wire is prohibited, you must use a 4-wire
power supply cabJe. See Figure 4. Failure to heed
this warning may resuk in electrocution or other
serious personal injury,
tf cooktop is used in a new branch circuit
installation (1995 NEC), mobile home, recreationaJ
vehicle, or where tocal codes DO NOT permit
grounding to the neutral (white) wire (see figure 4):
1. Disconnect tile power supply.
2. In the circuit breaker, fuse box or junction box,
connect appliance and power supply cable wires as
shown in figure 4.
Cable from Power Supply
/__..___ _White Wire
/___ _Junction Box
Green Wire (Ground) ____ U.L-Listed Conduit
Connector
Cable from appliance
Figure 4 - 4-WIRE GROUNDED JUNCTION BOX
tf connecting to a 4-wire power supply
cable etectrkal system, the appliance frame
connected ground wire MUST NOT be connected to
the neutrat wire of the 4-wire eJectricaJ system.
NOTE TO ELECTRICIAN: The armored cable leads
supplied with the appliance are Ublisted for connection
to larger gauge household wiring. The insulation of the
leads is rated at temperatures much higher than
temperature rating of household wiring. The current
carrying capacity of the conductor wire is governed by
tile temperature rating of tile insulation around the wire,
rather than tile wire gauge alone.