Installation Guide
ELECTRICAL CONNECTIONS
9
ENGLISH
4-WIRE CONNECTION WITH A 
POWER SUPPLY CORD
 • Only a 4-conductor power-supply cord kit rated 
120/240 volts, 50 amperes and marked for use with 
ranges, with closed loop connectors or open-end 
spade lugs with upturned ends, shall be used. The 
middle (neutral) wire of the power cord or 4-wire 
conduit must be connected to the middle post of 
the main terminal block. The other two wires of 
the power cord or conduit must be connected to 
the outside posts of the main terminal connection 
block. The 4th ground wire must be connected to 
the frame of the range with the ground screw.
− Failure to do so can result in electrical shock, 
severe personal injury or death.
 WARNING
Follow the instructions under “CONNECT RANGE CORD” 
on page 7 to correctly install the strain relief.
1.  Remove the lower 3 screws from the terminal block and 
retain them. (Refer to Figure 9.)
2. Remove the ground screw and bend the end of the 
ground strap up so the slot is over the hole of the center 
screw removed in step 1.
3.  Insert the ground screw into the power cord ground wire 
terminal ring and secure it to the range frame.
4.  Insert the 3 screws through each power cord terminal 
ring and into the lower terminals of the terminal block. 
Make sure that the center wire (white/neutral) is 
connected to the center lower position of the terminal 
block.
Tighten the 3 screws securely into the terminal block. The 
center screw now attaches the bent up ground strap to 
the block.
5. Go to page 11.
4-wire connection
Terminal 
block
Conduit
connection plate
Ground screw
Bend strap up and 
attach
Ground strap
Black White Red
FIGURE 9
3-WIRE CONNECTION: CONDUIT
Install the conduit as follows:
Remove the conduit connection plate from the rear of lower 
oven and rotate it as shown in Figure 5. The conduit hole 
(1
1
/8") must be used.
First, prepare the conduit wires as shown in Figure 10.
  3 wire  4 wire
Conduit
connection 
plate
 or 
Ground 
wire
FIGURE 10
Second, install the conduit strain relief as shown in Figure 6.
For conduit installations, purchase a strain relief and insert 
it into the 1 1/8" (2.8 cm) conduit hole. Then install the 
conduit through the body of the strain relief and fasten the 
strain relief with its ring. Reinstall the bracket.
For conduit connections :
If the wire in the conduit is copper it must be 8 or 10 AWG 
wiring.
If the wire in the conduit is aluminum it must be 6 or 8 
AWG wiring.
1.  Loosen the lower 3 screws from the terminal block. (Refer 
to Figure 11.)
2.  Insert the bare wire (white/neutral) end through the 
center terminal block opening. 
Do not remove ground strap connections.
3.  Insert the two side bare wire ends into the lower left and 
the lower right terminal block opening.
Tighten the 3 screws securely into the terminal block. 
(approximately 35 - 50 IN-LB)
4. Go to page 11.
3-wire connection
Terminal 
block
Wire ends
Conduit
connection plate
Black White Red
FIGURE 11










