Installation guide

Venting
The microwavehoodis set forventless (recirculating)
installation. Forwall or roofventingchangestothe
ventingsystemmustbe made.
CAUTION: To reduce risk of fire and to
properly exhaust air, be sure to vent air
outside. Do not vent exhaust air into
spaces within walls or ceilings or into
attics, crawl spaces or garages.
Forwall or rootventingmethods:
Choose betweenroof venting or wall venting.
If the wall exhaust method is chosen, be sure that there is
proper clearancewithin the wall for the exhaustvent.
Vent materialsneededfor installationare notincluded.
Wall and roofcapsmusthaveback-draftdamper.
We recommend:
v' using rigid metal vent.
v' that length of vent and number of elbows should be
kept to a minimum to provide efficient performance.
v' that size of vent should be uniform.
v' using duct tape to seal all joints in the vent system.
v' using caulking compound to seal exterior wall or roof
opening around cap.
v' two elbows should not be installed together.
We do NOTrecommend:
v' flexible metal vent.
NOTE:If flexible metal vent must be used, calculate each
foot of flexible metal vent as two feet of rigid metal vent.
Flexiblemetal elbows count twice as much as standard
elbows.
Vertical venting
Salida de aire per el cielo raso
root cap
caperuzade cielo raso
3-1/4"x 10"through-the-roof
a tray,s delcielorasoperun orificio
de3-1/4"x 10
Wall venting
Salida de alre p0r la pared
wallcap
caperuzadepared
3-1/4" x 10" through-the-wall
a trav6s do la paredper on
orificio de 3-1/4" x 10
Roundventtransition
Transici6nde conductode salidade aire redondo
roof cap __
6" min. diameter round wail cap
cooductode salida de aire ] ,"-_'1-... ...... _/,,=n_,r,tT=
redondode 6" de di_metro I" I ' "..'o--,K_,_._.C.",_,
miuimo :_ % u_ pa,_u
code
_ -114"x10"to 6"roundvent
transition
3" minimum height(required for
damper to fully open)
Altura minima de 3" (oecesaria
para quola compuertase abra
completamente)
transici6n de conductode salida
de aire redondode 3-1/4" x 10"
a 0"
Salida de aire
Lacampanadel hornoha side disefiadapara ser instalada
sin salida de aire (recirculaci6n). Para salida de aire en la
paredo en el cielo raso, deben hacersecambiosen ei
sistemade salida deaire.
PRECAUCION: para reducir el riesgo de
incendio y para instalar el sistema de
salida de aire adecuado, aseg_rese de
que el aire salga al exterior. No ponga la
salida de aire en espacios dentro de
paredes o cielos rases o en _ticos,
sbtanos de pequefia altura o garajes.
Param6todos desaiida de aire a trav6s de la pared o el
cielo raso:
Decidaentre instalar la salida de aire a trav6s del cielo raso o
de una pared.
Si se decide por el m_todo de salida de aire a trav6s de la
pared, aseg_resede que haya el espacio adecuado dentro de
la pared para el conducto de salida de aire.
No se incluyenlos materialesdel conductode salida deaire
que se necesitanpara la instaiaci6n.
Lascaperuzaspara cielorasoy pareddebentenor
compuertadecontratiro.
Recomendamos:
v' usar un conducto de salida de aire met_lico y rigido.
v" que la Iongitud del conducto de salida de aire y el n_mero
de codos se mantengana un minimo para Iograr un
rendimiento eficiente.
v" que las dimensiones del conducto sean uniformes.
v" usar cinta paraconducto para sellar todas las uniones en el
sistema de salida de aire.
v" usar masilla para calafatear para sellar la pared exterior o la
abertura en el cielo raso alrededor de la caperuza.
v" no se deben instalar dos codos juntos.
NO recomendamos:
v" conducto de salida de aire met_lico flexible
NOTA:si debeusarse un conducto met_lico flexible, calcule
cada pie de conducto met_lico flexible como si fueran dos pies
de conducto met_lico rigido. Los codos de metal flexible hacen
por dos codos est_ndar.
6
Recommendedventlength:
Use3-1/4" X 10" rectangular or 6" round vent.
The total length of the vent system including straight vent,
elbow, transitions, wall or roof caps must not exceedthe
equivalent of 140 feet of 3-1/4_X 10" rectangular or 6"
diameter round vent.
For best performance, use no more than three 90 degree
elbows.
To calculatethe length of system you need,add the
equivalent feet for each vent piece used in the system. See
the following examples:
3-1/4"x 10" ventsystem:
1 - 3-1/4" x 10"
90° elbow = 25 ft.
1 - wall cap = 40 ft.
8 feet straight 8 ft.
Length of
3-1/4" x 10" system = 73 ft.
6"vent system:
1 -transition = 5 ft.
2 - 90° elbows 20 ft.
1 - wall cap = 40 ft.
8 feet straight 8 ft.
Length of 6" system = 73 ft.
If the existing vent is round, a rectangular-to-round adapter
must be used and a rectangular 3" extension vent between
the damper assembly and adapter must be installedto
preventdamper from sticking.
Recommendedstandardfittings
Accesoriosest;Zndarrecomendados
3-1/4"x 10"to 6"=5 it.
De3-1/4"x t0" a6"=
5pies
3-1/4"x t0" roofcap=24 ft.
Caperuzadecielorasode
3-1/4"x 10"=24 pies
3-1/4"x 10"
90° dbow = 25ft.
Codode90° y 3-1/4'x
10"=25 pies
90° elbow=l0 ft.
Codede90° =
10pies
3-1/4"x 10"wallca
=40 ft.
Caperuzadepared
de3-1/4"x 10"=
40 pies
45° elbow=5ft.
Codode45o=
5 pies
_i iili_'
'iliiii!iiiiiiiiiiiiiiii_,,_eiiiiiiiilliiiiiiiii'
3-1/4"x10"flat
eJbow= 10ft.
Codopianode3-1/4"
x 10"= 10 pies
3-1/4"x 10"ventsystem
Sistemade salidade aire de 3-1/4"x 10"
3-1/4" x 10"
90° elbow
Code de go° y 6 It.
3-1/4"x1_ _6pies_ p. wallcap
Y I I II_ caperuzade
' It'> pared
2_. (2 pies)
6"vent system
Sistemade salidade aire de 6"
go°elbows
codede90=
2
transition
traosici6o
2 ft. (2 pies)
Longitudrecomendadadel conductode salida de aire:
Useun conducto de salida de aire rectangularde 3-1/4 _x 10"
o redondo de 6".
La Iongitud total del sistema de salida de aire, incluyendo el
conducto de salida de aire recto, el codo, las transiciones, las
caperuzas de pared o cielo raso no deben excederel
equivalente a 140 pies deconducto rectangular de salida de
aire de 3-1/4"x 10" o conducto redondo de 6" de di_metro.
Paramejores resultados, no use m_s detres codos de 90°.
Paracalcular la Iongitud del sistema que necesita,agregue la
equivalencia en pies paracada pedazode conducto usadoen
el sistema. Vea los siguientes ejemplos:
Sistemade salidade aire de 3-1/4"x 10":
1 -Codo de 90°
y 3-1/4" x 10" = 25 pies
1 - Caperuzade pared = 40 pies
8 pies recto = 8 pies
Longitud de un
sistema de 3-1/4_'x 10" = 73 pies
Sistemade salidade aire de 6":
1 -transici6n = 5 pies
2 - codos de 90° 20 pies
1 - caperuzade pared = 40 pies
8 pies recto 8 pies
Longitud de un
sistema de 6" = 73 pies
Si el actual conducto de salida deaire es redondo, debe usarse
un adaptador de rectangular a redondo y un conducto de
extension rectangular de 3" entre el conjunto de la compuerta
y se debe instalar el adaptador pare evitar que la compuerta se
atasque.
7