Technical data

MultiSensors
According to the two types of installation "Plug‘n Play" or "wired connection" you can find all connections of
the MultiSensor in the following overview. To remove the cover pull the sides of the case a bit apart. The
cover slips right out of the groove and can easily be lifted off (see section 5.6 - „How to open the
MultiSensor“). You can push the RF „learn button“ or insert the fixed connection cable from the rear of the
chassis. Break out the push-out marking from the inside out with a screwdriver. The spring-terminal is
designed for wire sizes up to 0.8 mm ². Use a screwdriver for slotted grub screws to fix the wires. They can
be inserted and removed without force.
Mounting instructions for MultiSensor-RF / -LAN / -LAN-RF
The MultiSensor is equipped with various individual sensors. To get an optimal sensitivity and function of the
sensors, please note the following installation instructions.
Note the following instructions:
Do not install close to heaters or direct heat.
Avoid detection of moving objects such as fans, plants, trees, flags, etc.
Don´t cover the Sensor. The PIR-Sensor needs inter-visibility for detection.
Coverage of the integrated PIR movement detector
The range of the MultiSensor is depending on the configured sensitivity about 8m. You get the best results,
when objects/persons move past the MultiSensor.
ceiling suspension wall fastening
Page 22 ! ! ! ! (08-2014, subject to change) kentix.de