Technical data

Configuration - EnergySensor
With the following settings set the limits for the alarm triggering of the energy sensors. If an alarm is
triggered, e-mails will be sent to the configured users and the buzzer is activated.
The configuration has to be made for each PDU.
Name
Assign the displayed name for each PDU.
On an alarm the name will also be shown in the notification (e-mail / SMS).
Line voltage / frequency
Sets the regional dependent default values for the external power supplement. This are also the base values
for the error detection and the energy measurement.
Active power / Voltage / Current
Define a minimum and maximum value for each measured value to monitor the energy measurement.
The minimum values are set to 0 in delivery state. After commissioning and configuration the value range
can be redefined to detect e.g the power failure of an end-device. Find the exact limits for each value in the
data-sheet.
Frequency
Enter a limit as tolerance for an fluctuation of the power frequency.
Reference value is 50 Hz or 60 Hz. Adjustment range is 0,1 bis 1,0 Hz (Default value: 0,1 Hz).
Flicker / Swell / Peak
Flicker and Swell are short-term fluctuations of the supply voltage.
Flicker here is a voltage drop, Swell a voltage overshoot.
For the monitoring of both values a tolerance in percent (related to the nominal voltage) and the number of
half-waves to view has to be set.
Peak
Peak is the highest occurring voltage during the normal operation (amplitude).
For the monitoring an upper threshold value of this amplitude voltage can be set. This exceeding is also
called peak or peak-alarm (default value: 400V).