Technical data

Kentix IO-Modules
The AlarmManager-PRO can be extended by additional digital Inputs and Outputs via special Expansion
modules. For this 2 external modules (KIO7052 with 8 digital Inputs / Outputs and KIO7053 with 16 digital
Inputs) are available.
Both modules are configured via a Web browser and are queried by the AlarmManager over the network.
Commissioning and Configuration
Depending on the module type it can be powered via PoE or with an external power supply. Using a power
supply it is necessary to regard the information in the data sheet, or only to use a power supply delivered by
Kentix. Information for the wiring of the In- and Outputs can also be found in the data sheet.
No
Step
Comment
1
Connect the network port E1 to a network switch with PoE support.
Connect your PC to this switch respectively establish a network
connection.
If you use a switch without PoE establish
power supply via the connectors (R)+Vs and
(B)-GND. Use the supplied power adapter-
cable
2
Open the Web-Interface of the module via the default IP 192.168.255.1
and change the IP-settings in „Network Settings“ to your required settings.
Default username and password: Admin/Admin
In the section „Web HMI“ the Inputs and
Outputs of the module can be monitored for
test purposes.
3
Start the Kentix ControlCenter and open the configuration of the I/O-
module via „Settings“ -> „Advanced...“ -> „External Alarms“
Select the module type and set the configured
IP-address.
4
Proceed with the setup for the wired external Inputs:
Enter a name for the alarming and choose alarm assignment and the
alarm logic. Eventually enter another alarm delay (default 1 sec.). Also
select an alarm zone for every used input.
In the module KIO7052 for each alarming
state one of the 8 Outputs is switched. Find
the assignment of the Outputs in the data
sheet of the module.
5
Save the configuration. After this the settings are directly active.
For testing purposes the state of the alarm
inputs can be monitored in the table
„MultiSensor Monitoring“.
Terminal assignment KIO7052
Terminal assignment KIO7053
Page 54 ! ! ! ! (08-2014, subject to change) kentix.de