Technical data

Data sheet MultiSensor-RACK (KMS-RACK)
Connectable devices
Stand-Alone operation (Integrated Web-Server)
AlarmManager-PRO
Sensor - temperature
range -20 to 99°C / -3 to 210°F (exactness ± 0,5°)
Sensor - Relative humidity
range 0 to 100% (exactness ± 3%)
Dew point
calculated in °C/°F
Sensor - motion
3 axes vibration sensor (adjustable)
Sensor - carbon monoxide (CO)
Fire detection via CO-Sensor
Internal resolution: 20-200ppm (0-100%) adjustable
Sensor-lifetime: 5 years (replaceable)
Buzzer
85dB, 2.3kHz
Sensor - external alarm inputs / outputs
2 Kentix System-jacks (SYS 1/2) to connect external Plug´n Play modules (RJ45)
like door contacts , leakage-sensors, external alarms.
Assignment:
2 x Alarm input (Armed-Active, Always-Active)
2 x Open Collector output 0.1A/12V (1x Alarming, 1x Remote control)
Sensor-Energy measurement
Voltage (V), Current (A), Active Power (W), Apparent power (VAR), Consumption
(kWh), Power factor (%), Consumption total (kWh), Consumption per month (kWh),
Costs (Currency)
Display
OLED Display to display the actual measurement values
LEDs to display ALARMs and RUN
LAN
10/100 Mbit LAN connection (IEEE 802.3)
integrated web-Server
SNMP - Data Interfaces
(Simple Network Management Protocol)
SNMP/V2 (write/read) and SNMP Traps
XML Data-export for measured values
Power supply
100-240VAC, power consumption approx. 4W
Supply of PDU 1+2 with IEC-connector type C20/16A
PDU Connection
(Power Distribution Unit)
2 separate PDU with 4 IEC power outlets (C13/10A) per PDU with strain reliefs
Maximum power consumption 7.200VA with 3.600VA each for PDU-1/2
PDU-1 and PDU-2 separately switchable with timer- and reset-function
Measurement accuracy
(at 20°C ambient temperature)
Voltage (RMS 90-260V)! +/- 0,5%
Current (RMS 0,002-12A)! +/- 0,5%
Active power (1.5-2.760W)! +/- 0,5%
Protection PDU 1/2
4 pcs. 10A micro fuse (5x20mm), time-lag - TH 250V with extinguishant
Casing
IT-Rack 1 HE (44mm), mounting brackets for front and rear
Dimensions: 418 x 165 x 44 mm (B x T x H), weight 1.25kg
Environmental conditions
Temperature 0 - 45°C / 32 - 113°F
Humidity 5-95%, not condensing
Content of delivery
2 pcs. IEC power cable with 3m (Type: C20/C19), 19“ mounting-brackets
Accessories
Leakage sensor (KLS02P)
Power-Adapter (KIO1)
Approvals
CE
Page 62 ! ! ! ! (08-2014, subject to change) kentix.de