PXL-250Quick Start Guide
Input Device Configuration - 3 Inputs
• Door Sense normally closed
• Request to Exit normally open
• Global Unlock normally open, or
Auxiliary RTE A-Door normally open
2.0 Cable Requirements
RS-232 Serial Cable
• four conductor, shielded, stranded, AWG 24 wire (Belden 9534 or a larger gauge)
• 50 feet maximum length (per RS-232 industry specification - greater lengths are not recommended)
RS-485 Network Cable
• two conductor, shielded, twisted pair, stranded, AWG 24 wire (Belden 9501 or a larger gauge)
• 16,000 feet total network length
• refer to the Network Wiring
Application Note (P/N 01824-002) for specific network wiring information
Input Power
• two conductor, stranded, AWG 18 wire (Belden 8461 or a larger gauge)
• 200 foot maximum length for systems using an SB-293 with two readers
NOTE: On long power cable runs, the cable resistance causes a drop in voltage at the end of the cable run. Be sure your
power supply does provide 12 VDC at the end of the cable run.
Earth Ground
• Single conductor, AWG 18 wire (or a larger gauge)
1
Keri Systems Proximity Readers
• six conductor, shielded, stranded, AWG 24 wire (Belden 9536 or a larger gauge)
• four conductor, shielded, stranded, AWG 24 wire (Belden 9534 or a larger gauge) for the MS-4000 only (there is no
beeper or LED in the MS-4000)
• see Table 2 for maximum cable lengths
1. Ground wire is green with or without yellow tracer.
Table 2: Maximum Cable Lengths by Wire Gauge for
Proximity Readers
Cable Length by Wire Gauge
Reader Type 100 feet 250 feet 500 feet
MS-3000
AWG 24 AWG 24 AWG 24
MS-4000
AWG 24 AWG 24 AWG 24
MS-5000
AWG 24 AWG 24 AWG 24
MS-7000
AWG 24 AWG 24 AWG 20
MS-9000
AWG 24 AWG 22 AWG 18