Manual

3-17
3
Communicating with the FD-MH series
- DeviceNet Compatible Network Unit DL-DN1 Users Manual (FD-MH) -
3-3
Explicit Messaging
The DeviceNet master unit can issu e explicit messages to the DL-DN1 for the
following purposes:
"Issuing a Motion Command to a Sensor Amplifier" (page 3-19)
"Reading settings or status" (page 3-20)
"Reading data with decimal point" (page 3-21)
"Writing settings or status" (page 3-21)
"Locking Sensor Amplifiers" (page 3-22)
Shown below is the basic format used when the DeviceNet master unit issues a
command to the DL-DN1 and w
hen t
he DL-DN1 responds to the DeviceNet master
unit, respectively.
The number of bytes used in the class ID, instance ID, and attribute ID may
vary depending on the master unit. The format examples in this manual
assume 2 bytes for class ID, 2 bytes for instance ID, and 1 byte for attribute
ID. For details, refer to the instruction manual of the master device.
Basic Formats of Explicit Messaging
DeviceNet master unit DL-DN1 Sensor amplifier
Receive
Receive
Send
Send
Response
Command
Node
address
Service
Code
Attribute
ID
When normal
When abnormal
Node
address
Node
address
Service
Code
Service
Code
ClassID
InstanceID
Service data
Response data
Response data
Error code
Received size
Received size
Reference