3-2 I/O Communication
3-19
3
Communicating with the SK-1000 Series
- DeviceNet Compatible Network Unit DL-DN1 User’s Manual (SK-1000) -
Rewriting a setting value of a sensor amplifier
Available setting values: HI setting value (Bank0), Low setting value (Bank0)
Device assignments: "Rewrite setting value" (page 3-13)
The setting value to be rewritten is the values listed above. In case of
rewriting the setting value of a BANK number other than the values
listed above, see "Reading/Writing Settings or Status of a Sensor
Amplifier" (page 3-23).
When rewriting any setting or parameter other than listed above, use the
procedure described in "Reading/Writing Settings or Status of a Sensor
Amplifier" (page 3-23).
This example changes the HI setting value of ID01.
It assumes that the operating mode assigned to the device is 3-output mode.
(1)Write the new setting value in the "setting-value rewrite data." For details of
writable ranges, see "Command parameter list for SK-1000 series" (page 3-
28).
(2)Execute the "request to rewrite setting value" command (0 -> 1).
(3)After the setting v alue is rewritten, the "setting value rewrite complete" signal flips
from 0 to 1.
(4)If an error occurs during "setting value rewriting" on the sensor amplifier, the
"setting value rewrite error" signal flips from 0 to 1. (The output is an OR sum of
settings.) Check the value ent
ered in the "setting-value rewrite data.
"
(5)When the "request to rewrite setting value" command is set to 0, the "setting value
rewrite complete" and "setting value rewrite error" parameters flip to 0.
Point
Reference
PLC
(1)
Setting-value rewrite data
1234h
OUT area [m+4]
(2) (5)
Request to rewrite setting value
OUT area [m+3] BIT 0
(3)
Setting-value rewrite complete
IN area [n+8] BIT 0
(4)
Setting- value rewrite error
IN area [n+7] BIT 0
Sensor amplifier
Setting-value 1234h
1
0
1
0
1
0