3-3 Cyclic communication
3-15
3
Communicating with IG Series
- EtherNet/IP Compatible Network Unit DL-EP1 Userโs Manual (IG) -
๎ Warning code list
No warning code occurs in the DL-EP1 and in the IG Series sensor amplifiers
connected to the DL-EP1.
The data to the sensor amplifier is assigned to the OUT area of the EtherNet/IP
scanner.
๎ External Input (5 Words (10 Bytes)) assembly instance (Instance ID): 65H
ID numbers (ID01 to ID04) are assigned for each sensor amplifier according to the
number of sensor amplifiers. The ID numbers larger than the number of connected
sensor amplifiers and ID05 to ID15 are not assigned.
01H to
0AH
(Each
ID
number
)
0BH
Sensor amplifier
error 11 of each ID
number
Standard waveform error 1-4
Refer to the IG Series User's
Manual.
0CH
Sensor amplifier
error 12 of each ID
number
Communication error
0DH
Sensor amplifier
error 13 of each ID
number
Additional setting error
0EH
Sensor amplifier
error 14 of each ID
number
Calculation error
Error
ID
Number
Code Description Cause Actions
Assignment to OUT Area (Scanner to DL-EP1)
DL-EP1 data
Scanner's OUT area
Address 0
Address 1
Address 9
External Input
(Assembly Instance: 101)
1-byte (8-bit) data
Name
Address
(Byte)
bit7 bit6 bit5 bit4 bit3 bit2 bit1 bit0
External
Input
Request 1
(Zero shift)
0 ID08 . . . . . ID01
1
Reserved for
system
ID15 . . . . . ID09
External
Input
Request 2
(Timing)
2 ID08 . . . . . ID01
3
Reserved for
system
ID15 . . . . . ID09
External
Input
Request 3
(Reset)
4 ID08 . . . . . ID01
5
Reserved for
system
ID15 . . . . . ID09