User Manual
3-4 Message Communication
3-35
3
Communicating with the GT-70A Series
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (GT-70A) -
00H
90H
(144)
Current
Value 0 (ID
Number 1)
Indicates the current value 0 of the sensor of ID
number 1.
Parameter range:
-2147483648 to 2147483647 (initial value: 0)
RDINT
91H
(145)
to 98H
(152)
:
99H
(153)
Current
Value 0 (ID
Number 10)
Indicates the current value 0 of the sensor ID
number 10.
Parameter range:
-2147483648 to 2147483647 (initial value: 0)
RDINT
9AH
(154)
to 9FH
(159)
Reserved for system
A0H
(160)
Current
Value 1 (ID
Number 1)
Indicates the current value 1 of the sensor ID
number 1.
Parameter range:
-2147483648 to 2147483647 (initial value: 0)
RDINT
A1H
(161)
to A8H
(168)
:
A9H
(169)
Current
Value 1 (ID
Number 10)
Indicates the current value 1 of the sensor ID
number 10.
Parameter range:
-2147483648 to 2147483647 (initial value: 0)
RDINT
AAH
(170)
to AFH
(175)
Reserved for system
B0H
(176)
Sensor
Status Mask
Setting
Set up the condition to determine if the sensor
error or warning is a recoverable DL-EP1 error
(MS LED blinks in red). If mask is selected, MS
LED does not blink in red when a sensor error or
warning occurs.
Parameter range: 0 to 1 (initial value: 0)
0: Not mask
1: Mask
R/W UINT
B1H
(177)
Sensor
Connected
Number
Indicates the number of connected sensor
amplifiers.
Parameter range: 0 to 10 (initial value: 0)
RUINT
B2H
(178)
to C7H
(199)
Reserved for system
0300H
(768)
Error Code
(ID number
00)
Indicates the error code of ID number 0.
Parameter range: 0 to 65535 (initial value: 0)
RUINT
Instance
ID
Attribute
ID
Name Description
Attribute
Data
Ty p e