User Manual
3-4 Message Communication
3-39
3
Communicating with the GT-70A Series
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (GT-70A) -
Group3
03
60H
(864)
Group3 Entry
count
Indicates the number of items
(number of entries) that can be set in Group 3.
Parameter range: 7
RDINT
0361H
(865)
Key lock
Sets key lock.
Parameter range: 0 to 1 (initial value: 0)
0: Unlock
1: Key lock
R/W DINT
0362H
(866)
Bank
switching
state
*9
Reads the currently operating bank.
Parameter range: 0 to 3 (currently operating
bank)
R
DINT
Rewrites the operating bank.
Parameter range: 0 to 3 (initial value: 0)
0: Rewrites the operating bank with bank 0.
1: Rewrites the operating bank with bank 1.
2: Rewrites the operating bank with bank 2.
3: Rewrites the operating bank with bank 3.
W
DINT
0363H
(867)
Timing
status
*
10
Reads the timing status.
Parameter range: 0 to 1
0: The timing input is OFF or measurement is in
progress in self-timing mode.
1: The timing input is ON or measurement is not
in progress in self-timing mode.
R
DINT
Writes the timing status.
Parameter range: 0 to 1
0: Change was made during measurement.
1: Change was made during non-measurement.
W
0364H
(868) to
0366H
(870)
Reserved for system
0367H
(871)
Bar display
mode
Indicates bar display mode.
Parameter range: 0 to 1 (initial value: 0)
0: Bar display mode
1: OK/NG display mode
R/W DINT
0368H
(872) to
037FH
(895)
Reserved for system
Group4
0380H
(896)
Group4 Entry
count
Indicates the number of items (entries) that can
be set in Group 4.
Parameter range: 26
RDINT
0381H
(897)
Calculation
mode and
Setting
*11, *12
Indicates calculation mode.
Parameter range: 0 to 8 (initial value: 0)
0: OFF
1: Maximum value
2: Minimum value
3: Flatness
4: Mean
5: Standard difference
6: Torsion
7: Warp
8: Thickness
R/W DINT
Class
Attribute
ID
Name Description
Attribute
Data
Ty p e