- PROFIBUS DP Compatible Network Unit DL-PD1 User's Manual (GT-70A) -
Appendix
4
4-2
Data update time
The data update time for cyclic communication is shown below.
Maximum data processing time = (1) + (2) + (3) + (4)
(1)PROFIBUS DP master data update time
(2)Network data update time
(3)Data update time between the DL-PD1 and sensor amplifiers
(4)Sensor amplifier response time
For (1) and (2), see manuals for each model.
For (4), refer to the User's Manual of each sensor amplifier connected to the DL-PD1.
Number of connected
sensor amplifiers
Control output/Comparator value
Calculation function
OFF
Calculation function
ON
1 9ms 12.5ms
2 11ms 15.5ms
3 15ms 21.5ms
4 17ms 24.5ms
5 21ms 30.5ms
6 23ms 33.5ms
7 27ms 39.5ms
8 29ms 42.5ms
9 33ms 48.5ms
10 35ms 51.5ms
(4)(3)(2)(1)
DL-PD1 Sensor amplifierPROFIBUS DP master