User guide

2-3 Technical data
2-8
- PROFIBUS DP Compatible Network Unit DL-PD1 User's Manual (IL) -
Connection and Configuration
2
General Specifications
*1 "D-bus" is the name of KEYENCE's wiring-saving system for sensor amplifiers.
*2 Varies with the sensor amplifiers connected.
Model DL-PD1
PROFIBUS DP
specifications
Device type DP-V1 Slave (D-sub 9 pin, Number of the ports: 1)
Communication speed 9.6 kbit/s to 12 Mbit/s
Cable length
9.6 / 19.2 / 45.45 / 93.75 kbit/s: 1200 m
187.5 kbit/s: 1000 m
500 kbit/s: 400 m
1.5 Mbit/s: 200 m
3 / 6 / 12 Mbit/s: 100 m
Sensor amplifier
connection
specifications
Connectable sensor
amplifiers
Sensor amplifiers with D-bus support
*1
Number of connectable
sensor amplifier units
15 units max.
*2
Power voltage
20 to 30 VDC, including ripple (p-p) 10%
(This voltage is supplied from the connected sensor amplifier.)
Power consumption 1600 mW or less (65 mA max. at 24 V)
Environmental
resistance
Operating surrounding
air temperature
-20 to +55°C (no freezing)
Operating surrounding
air humidity
35 to 85% RH (no condensation)
Vibration resistance IEC60068-2-6 2G (10 to 500 Hz, 2 hours each in X, Y, Z direction)
Impact resistance IEC60068-2-27 30G (11 ms, 3 times each in X, Y, Z direction)
Materials
Main unit case and dust cover: Polycarbonate
PROFIBUS connector: Steel - Nickel plating
Weight (including connectors) Approx. 65 g