Manual
Table Of Contents

13
- PROFINET Communication Unit DL-PN1 User's Manual (GT2) -
*1 Functions assigned to the external input request 1 to 4 are as follows:
• External input request 1: PRESET input
• External input request 2: TIMING input
• External input request 3: RESET input
• External input request 4: ERROR CLEAR input
Refer to the GT2 series user's manual.
*2 If the judgment value is correct, the parameter range is -199.9999 to +199.9999.
• When the comparator value is over range, "+999.9999" is stored.
• When the comparator value is under range, "-999.9999" is stored.
• When the comparator value is invalid, "-999.9998" is stored.
• When an error occurs, "+1000.0000" is stored.
*3 When you use the calculation function and calculation setting is set to other than
standard difference display, a reading error occurs on the expansion unit.
89 External input response 4
When the request reception to
the "External input request 4"
is complete, the
corresponding bit is set.
*1
2byte
WORD
R
bit0 : Reserved for system
bit1 : Slot 1
:
bit15 : Slot 15
90 to
127
Reserved for system
128 Product code 1
Stores the product code of the
slot number 01 sensor
amplifier.
2byte
WORD
R
GT2-7** (main unit) : 4006
GT2-7**
(expansion unit) : 4007
GT2-71MC*: 4008
GT2-100* (main unit) : 4010
GT2-100*
(expansion unit) : 4011
:: : ::
142 Product code 15
Stores the product code of the
slot number 15 sensor
amplifier.
2byte
WORD
R
143 Reserved for system
144 Revision 1
Stores the revision of the slot
number 01 sensor amplifier.
2byte
WORD
R 0101H to FFFFH
:: : :: :
158 Revision 15
Stores the revision of the slot
number 15 sensor amplifier.
2byte
WORD
R 0101H to FFFFH
159 Reserved for system
160
Comparator value 0 (Slot
Number 1)
Used when reading
comparator value (P.V. value)
of slot number 01.
*2 *3
4byte
DINT
R
-199.9999 to +199.9999:: : ::
174
Comparator value 0 (Slot
Number 15)
Used when reading
comparator value (P.V. value)
of slot number 15.
*2 *3
4byte
DINT
R
175 Reserved for system
176
Number of decimal
places (Current value 0,
Slot Number 1)
Used when reading the
decimal position of slot
number 01 comparator value
(P.V. value).
4byte
DINT
R
:: : ::
190
Number of decimal
places (Current value 0,
Slot Number 15)
Used when reading the
decimal position of slot
number 15 comparator value
(P.V. value).
4byte
DINT
R
191 to
194
Reserved for system
Index
(DEC)
Function name Description
Data
type
Attribute Value