Instruction Manual
31
- PROFINET Communication Unit DL-PN1 User's Manual (IL) -
Rewrite the HI setting value
 Explanation of the program
 Network1
M6.0 (Address 6, Bit 0) turns ON, and the HI setting value to be set is written in IN.
The HI setting value to be set is written in MDxx. It is not yet applied at this point.
 Network2
When M6.0 (Address 6, Bit 0) and M9.0 (Address 9, Bit 0) are ON, READ command 
send processing is carried out.
The ID number of the amplifier (main unit) is written in ID, 65 (the Index number of the HI 
setting value) is written in INDEX, "4" is written in LEN, the read destination address is 
written in RECORD, and REQ turns ON.
The current HI setting value is written in the read destination address.
MOV
M6.0
EN ENO
IN OUT
MDxx
M9.1
M9.0
M6.0 M9.0
M9.1
EN ENO
REQ VALID
ID BUSY
INDEX ERROR
MLEN STATUS
RECORD LEN
M6.0 M9.2
M9.0
M6.0 M9.2
EN ENO
REQ VALID
ID BUSY
INDEX ERROR
LEN STATUS
MDxx RECORD
S
R
SFB53 "WR REC"
SFB52 "RD REC"
Network1
Network2
Network3
Network4
Network1
Read destination address
4 (fixed value)
65 (the Index number of the HI setting value)
HI setting value
Error information
ID number of the amplifier (main unit)
Status
 information
Reply data length
4 (fixed value)
65 (the Index number of the HI setting value)
Error information
ID number of the amplifier (main unit)
Status
 information