2-7 Non Safety-Related Outputs
2-24
GL-RHG-M-NO2-E
Functions and Features
2
Error output (Transmitter, black wire)
The error output is activated if the GL-RHG goes to the error condition.
See "Functions" (page 2-4) for the information of wiring system and cable type to activate this function.
Time chart
(1) When using a PNP output type cable to connect to a PNP input device, or when using an NPN output
type cable to connect to an NPN input device
(2) When using a PNP output type cable to connect to an NPN input device, or when using an NPN output
type cable to connect to a PNP input device
Muting lamp output (The red wire of the transmitter cable)
This output is available only when using an 11-core cable for the transmitter.
The muting lamp output is an output function to light up the muting lamp if the GL-RHG goes into the
muted condition or override condition. The muting lamp is used to indicate the condition of GL-RHG.
"Temporary Suspension of Safety Function" (page 2-7)
See "Functions" (page 2-4) for the information of wiring system and cable type to activate this function.
Muting lamp
When using the muting lamp, it must meet the following conditions.
For an incandescent lamp : rated 24 V DC, 1 to 5.5 W
For an LED indicator : rated current consumption must be 10 to 230 mA
Point
The muting lamp output is an NPN open collector output regardless of the cable type.